ULTRAGLOW DIRECT VENT SYSTEM (FLEX)

INSTALLATION

RIGID PIPE VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS

ULTRAGLOW DIRECT VENT SYSTEM (FLEX)

(Propane & Natural Gas)

The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o elbow (two 45o elbows equal one 90o elbow).

Note: Must use optional rigid pipe adaptor (Part # 510-994) when using rigid pipe vent systems.

All Rigid Pipe Systems 4" inner diameter

6-5/8" outer diameter

UltraGlow Flex Vent 4" inner diameter

6-7/8" inner diameter

A vent guard should be used when- ever the termination is lower than the specifi ed minimum or as per local codes.

Note: UltraGlow Direct Vent System (Flex) is only approved for hori- zontal terminations.

Maintain clearances to combustibles as listed on pages 7 and 8.

Horizontal vent must be supported every 3 feet.

Firestops are required at each floor level and whenever passing through a wall.