INSTALLATION

VENTING ARRANGEMENTS

HORIZONTAL TERMINATION (FLEX)

Regency® Direct Vent System

These venting systems, in combination with the L900E, have been tested and listed as a direct vent system by Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior Vent Termination Locations" section.

FPI Direct Vent (Flex) System Termination Kits include all the parts needed to install the L900E using a flexible vent.

INSTALLATION

FPI Kit #

Length

Contains:

#946-618

6 Feet

1)

8” fl exible liner (Kit length)

 

 

2)

5” fl exible liner (Kit length)

 

 

3)

spring spacers (3)

 

 

4)

thimble (2)

 

 

5)

AstroCap termination cap (1)

#946-616

10 Feet

6)

screws (12)

 

 

7)

tube of Mill Pac (1)

 

 

8)

plated screws (8)

 

 

9)

S.S. screws #8 x 1-1/2” drill point, (4)

 

 

10)

vinyl siding standoff

 

 

 

 

Vinyl Siding

Standoff

Wall Thimble

(Mandatory in all

Horizontal Terminations)

5” dia. flue pipe

 

8” dia.

spring spacer

Flue pipe

 

Vent Guard - if required*

(Part #946-506/P)

AstroCap XLTM

Termination Cap

(Part #946-623/P)

*A Vent Guard is required when the AstroCap is installed above grade at 7 feet or lower.

Notes:

1)Liner sections should be continuous without any joints or seams.

2)Only Flex pipe purchased from FPI may be used for Flex installations.

3)Horizontal vent must be supported every 3 feet.

4)Awallthimbleismandatoryforallhorizontalterminations due to high temperatures.

Regency® L900E Direct Vent Gas Fireplace

15

Page 15
Image 15
Regency L900E-NG installation manual Venting Arrangements, Horizontal Termination Flex, FPI Kit # Length Contains