Installing the New Water Heater (cont’d)
5.The water heater must be electrically “grounded” by the installer. The unit will not operate unless it is prop- erly grounded. For complete grounding details and all allowable exceptions, refer to local codes or in the
absence of local codes, with the National Electrical Code, ANSI/NFPA 70 (current edition).
6.Replace the wiring junction cover using the screws provided.
Wiring Diagram
CAUTION
Label all wires prior to disconnection when servicing con- trols. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
Venting
WARNING
To insure proper venting of this
WARNING
The vent outlet must connect to the water heater exhaust out- let. The vent inlet piping must connect to the water heater air inlet. Both the water heater connections are clearly marked. Failure to read this instruction can result in DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.
WARNING
The vent pipe from the water heater must be 3″ diameter vent pipe and must slope upward 1⁄8 inch per five linear feet.
All vent gases must be completely vented to the outdoors of the structure (dwelling).
MIN. RISE 1⁄8″
PER FIVE FEET
WARNING
Obstructed or deteriorated vent systems may present seri- ous health risk or asphyxiation.
WARNING
Failure to have required clearances between water heater and combustible material will result in a fire hazard.
13