Installing the New Water Heater (cont'd)

VENTING SYSTEM EXAMPLE INSTALLATIONS FOR ALL MODELS

The vent piping cannot under any circumstances be run downhill.

The vent piping can be installed as follows:

1. Horizontal runs require a minimum 1/8rise per five feet.

3ELBOW EXAMPLE

MIN. RISE 18

PER FIVE FEET

3 ELBOW

EXAMPLE

MIN. RISE 18

PER FIVE FEET

CAULK

JOINT

MIN. RISE 18

PER FIVE FEET

2.The total vertical and horizontal vent runs cannot exceed the maximum length with the number of 90˚ elbows as specified in the table below. If more elbows are required, the venting distance must be reduced 5 feet for every 90° elbow:

3DIA. VENTS

NUMBER OF 90˚ DEG.

MAX. LENGTH (FT.)

ELBOWS*

45

1

40

2

35

3

 

 

*NOTE: Two 45˚ elbows are equivalent to one 90° elbow. One 90˚ elbow equals 5 feet of equivalent vent length.

1 ELBOW

 

 

 

 

45MAX.

 

EXAMPLE

 

 

 

 

18MIN.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1114MIN.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1314MIN.

 

 

 

 

 

 

 

 

 

 

MIN. RISE 18

 

 

 

 

 

 

 

 

 

PER FIVE FEET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 ELBOW EXAMPLE

38

3 ELBOW EXAMPLE

MIN. RISE 18

7

MIN. RISE 18

PER FIVE FEET

ONE ELBOW

PER FIVE FEET

3.Minimum vent length for all models is 18 inches.