Additional Clearances - Vent Terminal

Additional Clearances - Vent Terminal

Local codes supersede these clearances.

Avoid termination locations near a dryer vent.

Avoid termination locations near commercial cooking exhaust.

For VA3237 air intake position, follow the ANS Z21.10.3 ● CSA 4.3 requirements on the previous page.

INSIDE Vent terminal (represents concentric vent terminal or VA3237 exhaust only vent terminal)

Manual background 12" Manual backgroundManual background

(0.30 m ) to an inside corner

(0.91 m) to ventilated or unventilated soffit

36" or eve vent; or to a deck or porch

VV Manual backgroundManual background 12"Manual background

(0.30 m) between Rinnai terminals at same level

V

60" (1.52 m) vertically between Rinnai terminals

V

24" (0.61 m) to wall or parapet

V

INSIDE

CORNER

(1.52 m) between

60"

Rinnai terminals

 

at different levels

V

V

12"

 

(0.30 m) between

V

V

Rinnai terminals at

same level

 

 