Flue Installation (R98LSi, R98LSi-ASME)
Air Intake Assembly | 1 |
The air intake system consists of a field supplied 4 inch diameter stainless steel, Schedule 40 PVC, ABS or CPVC pipe. A maximum 6 feet of
2 |
The air intake has a zero clearance to combustibles.
Air Intake Connection | 3 | 4 | |
1. | Drill 2 small holes at the end of the air intake | ||
| pipe. |
|
|
2. | Slide the pipe over the air intake terminal. |
|
|
3. | Using a level, ensure the pipe is straight up and |
|
|
| down. |
|
|
4. | With self tapping screws, attach the pipe to the air |
|
|
| intake terminal. |
|
|
5. | Apply a bead of silicone around the pipe and air |
|
|
| intake terminal, ensuring an air tight connection. |
|
|
Exhaust Pipe Assembly
Refer to the manufacturer’s installation instructions for the specific exhaust vent system.
Venting Clearances to Combustibles
| Enclosed | Unenclosed | |
Vent Size |
|
| |
Horizontal & | Horizontal & | ||
| |||
|
|
| |
4" (102 mm) | 4" (102 mm) | 1" (26 mm) | |
|
|
|
Horizontal Terminations
The air intake must be located in relation to the exhaust as shown below. The air intake must angle 1/4 inch per foot to the termination to prevent entry of rain.
6” |
|
Vent |
|
8” |
|
Optional |
|
Intake | EXHAUST |
Intake | COMBUSTION AIR / |
INTAKE | |
| SLOPE INTAKE AND EXHAUST |
The vent termination and air | TOWARD OUTSIDE TERMINATION |
MINIMUM 1/4" PER FOOT | |
intake must be in the same |
|
pressure zone and face the |
|
same direction. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
32 | VB Series Indoor LS Manual |
|
|
|
|
|
|
|
|
|
|