SECTION 14: GENERAL SPECIFICATIONS

SECTION 14: GENERAL SPECIFICATIONS

 

14.1 Material Specifications

14.3 Suspension Specifications

14.1.1 Reflectors

Hang heater with materials with a minimum working

.024 Aluminum

load of 75 lbs (33 kg). See Page 15, Figure 14.

(Optional .024 Stainless Steel Type 304)

14.4 Controls Specifications

14.2 Heater Specifications

Time switches, thermostats, etc. can be wired into

14.2.1 Ignition

the electrical supply. External controls supplied as an

Fully automatic, three-try, direct spark, electronic

optional extra.

 

ignition control, 100% safety shut-off.

General Specifications for BH-Series heaters are as follows:

End View

Side View

 

Reflector

 

 

 

 

 

 

 

 

 

12.5"

 

 

 

 

Turbulator (select models)

(32 cm)

 

 

 

 

 

 

 

 

 

 

12.5"

 

 

Burner Tube

Minimum Length A

 

 

11"

 

 

 

 

(32 cm)

 

 

 

 

 

(28 cm)

 

 

 

 

 

 

 

 

 

 

 

 

Heat Input Rate

Length “A”

Recommended

 

 

Minimum Mounting Height*

 

 

 

 

Model

(Btu/h) x (1000)

Minimum

Space

Spot

BH-40

40

10' (3 m)

8-10' (2.4 - 3 m)

8'(2.4 m)

BH-60

60

20' (6 m)

10-12' (3 - 3.6 m)

9' (2.7 m)

BH-80

80

20' (6 m)

12-15' (3.6 - 4.5 m)

11'

(3.3 m)

BH-100

100

30' (9 m)

12-15' (3.6 - 4.5 m)

12'

(3.7 m)

BH-115

115

30' (9 m)

15-20' (4.5 - 6 m)

15'

(4.6 m)

BH-125

125

40'

(12 m)

15-20' (4.5 - 6 m)

15'

(4.6 m)

BH-140

140

40'

(12 m)

20-25' (6 - 7.6 m)

20'

(6.1 m)

BH-150

150

50'

(15 m)

20-25' (6 - 7.6 m)

20'

(6.1 m)

BH-175

175

50'

(15 m)

25' (7.6 m)

23' (7 m)

BH-200

200

60'

(18 m)

25' (7.6 m)

25'

(7.6 m)

*See Page 5, Section 3 for clearances to combustibles.

GAS PRESSURE AT MANIFOLD:

Natural Gas:

3.5" wc

LP Gas:

10.5" wc

PIPE CONNECTION:

1/2" NPT (for BH-40, 60, 80, 100, 115 & 125) 3/4" NPT (for BH- 140, 150,175 & 200)

DIMENSIONS:

Vent Connection Size: 4" (10 cm)

Outside Air Connection Size: 4" (10 cm)

Refer to figure above for dimensional information.

GAS INLET PRESSURE:

 

 

Natural Gas:

 

 

for BH-40, 60, 80, 100,

 

 

115, 125, 140, 150

4.6" wc Minimum

for BH-175, 200

5.0" wc

Minimum

 

14.0" wc

Maximum

LP Gas:

11.0" wc

Minimum

 

14.0" wc Maximum

ELECTRICAL RATING (ALL MODELS):

120 V - 60 Hz, 1 A