COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL
4.4General Technical Data Table (all models) Appliance Category II 2H/L 3B/P
Model |
| 015 | 020 |
| 030 |
| 040 |
| 050 | 060 | 070 |
| 080 | 0100 |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Electrical Supply* |
|
|
| 230 | V / 50 Hz / 1 Ø |
|
|
| 400 V / 50 Hz / 3 Ø |
| ||||
Main Fan Motor Type |
|
|
|
| Direct Drive |
|
|
|
| Belt Drive |
| |||
Motor Size | (kW) |
| 0.75 |
|
|
|
| 2.2 | 1.5 |
| 2.2 | 4.0 | ||
Motor Pulley | (PCD) |
|
|
| NA |
|
|
| 2 A x | 2 A x 95 mm | 2 A x | |||
|
|
|
|
|
| 80 mm | 106 mm | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Fan Pulley | (PCD) |
|
|
| NA |
|
|
| 2 A x | 2 A x |
| 2 A x | 2 A x | |
|
|
|
|
|
| 180 mm | 180 mm |
| 180 mm | 180 mm | ||||
|
|
|
|
|
|
|
|
|
|
| ||||
Start Current | (Amps) | 24 | 24 |
| 28 |
| 21 |
| 21 | 10.2 | 30 |
| 30 | 35 |
Run Current | (Amps) | 5.3 | 5.3 |
| 6.3 |
| 6.2 |
| 6.2 | 3.5 | 5.1 |
| 5.1 | 9.6 |
Airflow | (m3/h) | 3398 | 3398 |
| 5097 |
| 6796 |
| 8495 | 11044 | 12443 |
| 12443 | 17330 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Free Blowing | (ft3/min) | 2000 | 2000 |
| 3000 |
| 4000 |
| 5000 | 6500 | 7500 |
| 7500 | 10200 |
NOTE: *Models 40 & 50 are available with 230 V 1 Ø electrical supply as an extra cost option. A permanent uninterrupted electrical supply is required for all models.
When reading the following data tables, ensure that you are using the correct table for the burner and gas valve installed. The data tables include a burner reference letter that can be found on the heater data plate. Refer to the burner manufacturer’s instructions and the specific instructions supplement where applicable. The burner settings shown in the instructions must be used for burner settings.
4.5 Technical Data - Ecoflam ON/OFF Burners (all models - burner reference "C")
Model |
| 015 |
| 020 |
| 030 | 040 | 050 | 060 | 070 | 080 | 0100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Gross Heat Input | (kW) | 55.5 |
| 73.3 |
| 93.2 | 129.9 | 162.0 | 208.0 | 242.0 | 275.2 | 348.5 |
(Btu/h) x (1000) | 189.4 |
| 250.1 |
| 318.0 | 443.2 | 552.7 | 709.7 | 825.7 | 939.0 | 1189.1 | |
|
|
| ||||||||||
Net Heat Input | (kW) | 50.0 |
| 66.0 |
| 84.0 | 117.0 | 146.0 | 187.4 | 218.0 | 248.0 | 314.0 |
(Btu/h) x (1000) | 170.6 |
| 225.2 |
| 286.6 | 399.2 | 498.2 | 639.4 | 743.8 | 846.2 | 1071.4 | |
|
|
| ||||||||||
Heat Output | (kW) | 47.4 |
| 61.2 |
| 78.4 | 110.2 | 134.5 | 177.7 | 205.3 | 230.4 | 293.4 |
(Btu/h) x (1000) | 161.7 |
| 208.8 |
| 267.5 | 376.0 | 458.9 | 606.3 | 700.5 | 786.1 | 1001.1 | |
|
|
| ||||||||||
Pressure Switch Setting | (mbar) |
| 1.5 |
| 4.5 | 4.0 | 6.5 | 5.0 | 6.5 | 7.5 | 7.0 | |
Flue Static Pressure | (mbar) |
|
| 0.10 | 0.45 | |||||||
Gas Connection | (in) |
|
| 3/4" |
|
|
|
| 1 1/4" |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
Natural Gas (G20) Data - Inlet Pressure 20 mbar (7.8 in WG) | Min 17 mbar (6.8 in WG) | Max 25 mbar (10 in WG) | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
Main Burner Gas Pressure | mbar | 4.0 | 2.7 | 4.2 | 4.8 | 7.7 | 5.2 |
| 7.1 | 9.5 | 10.0 |
Start Gas Pressure | mbar | NA | NA | NA | 1.8 | 2.8 | 0.9 |
| 1.1 | 1.7 | 3.4 |
Gas Rate | (m3/h) | 5.3 | 7.0 | 8.9 | 12.4 | 15.4 | 19.8 |
| 23.1 | 26.2 | 33.2 |
(ft3/h) | 187 | 247 | 314 | 438 | 546 | 701 |
| 816 | 928 | 1175 | |
Start Gas Orifice | (mm dia) |
|
|
| 5.0 | 6.0 | 7.0 |
| 7.0 | 7.0 |
|
Burner Type |
| AZUR 60 | BLU 120 | BLU 120 | BLU 170 | BLU 250R | BLU 250 | BLU 250 | BLU 250S | BLU 350 | |
Burner Head |
| S | S | S | S | S | S |
| S | S | S |
Burner Head Setting | (mm) | 0 | 10 | 11 | 15 | 14 | 24 |
| 24 | 24 | 21 |
Air Setting |
| 2.6 | 4.2 | 6 | 2.2 | 3.5 | 2.9 |
| 3.6 | 1.4 | 1.6 |
Valve Type Main Gas |
|
| MBDLE |
| MBDLE |
|
| MBDLE |
| MBDLE | |
|
| 405 |
| 407 |
|
| 410 |
| 412 | ||
|
|
|
|
|
|
| |||||
Valve Type Start Gas |
|
| NA |
|
|
| S.I.T. 0 832 051 |
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
LPG Gas Propane (G31) Data - Inlet Pressure 37 mbar (14.6 in WG) | Min 25 mbar (10 in WG) | Max 45 mbar (18 in WG) | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
Main Burner Gas Pressure | mbar | 4.2 | 3.3 | 4.6 |
| 4.8 | 7.5 | 5.8 | 7.8 | 12.0 | 7.6 |
Start Gas Pressure | mbar | NA | NA | NA |
| 1.6 | 2.5 | 0.8 | 1.0 | 1.5 | 3.1 |
Gas Rate | (m3/h) | 2.1 | 2.8 | 3.5 |
| 4.9 | 6.1 | 7.8 | 9.1 | 10.4 | 13.1 |
(kg/h) | 3.9 | 5.1 | 6.5 |
| 9.1 | 11.3 | 14.5 | 16.9 | 19.2 | 24.3 | |
|
| ||||||||||
Start Gas Orifice | (mm dia) |
|
|
|
| 5.0 | 6.0 | 7.0 | 7.0 | 7.0 |
|
Main Gas Orifice | (mm dia) | 8.5 | 10.0 | 10.0 |
| 14.5 | 14.5 | 14.5 | 14.5 | 14.5 |
|
Burner Type |
| AZUR | BLU | BLU |
| BLU | BLU | BLU | BLU | BLU | BLU |
| 60 AH | 120 AH | 120 AH |
| 170 AH | 250R AH | 250 AH | 250 AH | 250S AH | 350 AH | |
|
|
| |||||||||
Burner Head |
| S | S | S |
| S | S | S | S | S | LPG |
Burner Head Setting | (mm) | 0 | 10 | 13 |
| 15 | 14 | 24 | 24 | 24 | 20 |
Air Setting |
| 3.0 | 4.8 | 6.6 |
| 2.6 | 4.5 | 3.1 | 4.2 | 1.6 | 1.8 |
Valve Type Main Gas |
|
| MBDLE |
|
| MBDLE |
| MBDLE |
| MBDLE | |
|
| 405 |
|
| 407 |
| 410 |
| 412 | ||
|
|
|
|
|
|
| |||||
Valve Type Start Gas |
|
| NA |
|
|
|
| S.I.T. 0 832 051 |
|
|
NOTE: For adjustment of head setting, see Ecoflam Instructions