Roberts Gorden POP-ECA/PGP-ECA 015 to 0100 Model, Max 25 mbar 10 in WG, Max 45 mbar 18 in WG

Models: POP-ECA/PGP-ECA 015 to 0100

1 62
Download 62 pages 45.64 Kb
Page 14
Image 14
Max 25 mbar (10 in WG)

COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL

4.4General Technical Data Table (all models) Appliance Category II 2H/L 3B/P

Model

 

015

020

 

030

 

040

 

050

060

070

 

080

0100

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Supply*

 

 

 

230

V / 50 Hz / 1 Ø

 

 

 

400 V / 50 Hz / 3 Ø

 

Main Fan Motor Type

 

 

 

 

Direct Drive

 

 

 

 

Belt Drive

 

Motor Size

(kW)

 

0.75

 

 

 

 

2.2

1.5

 

2.2

4.0

Motor Pulley

(PCD)

 

 

 

NA

 

 

 

2 A x

2 A x 95 mm

2 A x

 

 

 

 

 

 

80 mm

106 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Pulley

(PCD)

 

 

 

NA

 

 

 

2 A x

2 A x

 

2 A x

2 A x

 

 

 

 

 

 

180 mm

180 mm

 

180 mm

180 mm

 

 

 

 

 

 

 

 

 

 

 

Start Current

(Amps)

24

24

 

28

 

21

 

21

10.2

30

 

30

35

Run Current

(Amps)

5.3

5.3

 

6.3

 

6.2

 

6.2

3.5

5.1

 

5.1

9.6

Airflow

(m3/h)

3398

3398

 

5097

 

6796

 

8495

11044

12443

 

12443

17330

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Free Blowing

(ft3/min)

2000

2000

 

3000

 

4000

 

5000

6500

7500

 

7500

10200

NOTE: *Models 40 & 50 are available with 230 V 1 Ø electrical supply as an extra cost option. A permanent uninterrupted electrical supply is required for all models.

When reading the following data tables, ensure that you are using the correct table for the burner and gas valve installed. The data tables include a burner reference letter that can be found on the heater data plate. Refer to the burner manufacturer’s instructions and the specific instructions supplement where applicable. The burner settings shown in the instructions must be used for burner settings.

4.5 Technical Data - Ecoflam ON/OFF Burners (all models - burner reference "C")

Model

 

015

 

020

 

030

040

050

060

070

080

0100

 

 

 

 

 

 

 

 

 

 

 

 

 

Gross Heat Input

(kW)

55.5

 

73.3

 

93.2

129.9

162.0

208.0

242.0

275.2

348.5

(Btu/h) x (1000)

189.4

 

250.1

 

318.0

443.2

552.7

709.7

825.7

939.0

1189.1

 

 

 

Net Heat Input

(kW)

50.0

 

66.0

 

84.0

117.0

146.0

187.4

218.0

248.0

314.0

(Btu/h) x (1000)

170.6

 

225.2

 

286.6

399.2

498.2

639.4

743.8

846.2

1071.4

 

 

 

Heat Output

(kW)

47.4

 

61.2

 

78.4

110.2

134.5

177.7

205.3

230.4

293.4

(Btu/h) x (1000)

161.7

 

208.8

 

267.5

376.0

458.9

606.3

700.5

786.1

1001.1

 

 

 

Pressure Switch Setting

(mbar)

 

1.5

 

4.5

4.0

6.5

5.0

6.5

7.5

7.0

Flue Static Pressure

(mbar)

-0.05

 

-0.05

 

-0.09

-0.30

-0.05

-0.25

-0.17

0.10

0.45

Gas Connection

(in)

 

 

3/4"

 

 

 

 

1 1/4"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural Gas (G20) Data - Inlet Pressure 20 mbar (7.8 in WG)

Min 17 mbar (6.8 in WG)

Max 25 mbar (10 in WG)

 

 

 

 

 

 

 

 

 

 

 

 

Main Burner Gas Pressure

mbar

4.0

2.7

4.2

4.8

7.7

5.2

 

7.1

9.5

10.0

Start Gas Pressure

mbar

NA

NA

NA

1.8

2.8

0.9

 

1.1

1.7

3.4

Gas Rate

(m3/h)

5.3

7.0

8.9

12.4

15.4

19.8

 

23.1

26.2

33.2

(ft3/h)

187

247

314

438

546

701

 

816

928

1175

Start Gas Orifice

(mm dia)

 

 

 

5.0

6.0

7.0

 

7.0

7.0

 

Burner Type

 

AZUR 60

BLU 120

BLU 120

BLU 170

BLU 250R

BLU 250

BLU 250

BLU 250S

BLU 350

Burner Head

 

S

S

S

S

S

S

 

S

S

S

Burner Head Setting

(mm)

0

10

11

15

14

24

 

24

24

21

Air Setting

 

2.6

4.2

6

2.2

3.5

2.9

 

3.6

1.4

1.6

Valve Type Main Gas

 

 

MBDLE

 

MBDLE

 

 

MBDLE

 

MBDLE

 

 

405

 

407

 

 

410

 

412

 

 

 

 

 

 

 

Valve Type Start Gas

 

 

NA

 

 

 

S.I.T. 0 832 051

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LPG Gas Propane (G31) Data - Inlet Pressure 37 mbar (14.6 in WG)

Min 25 mbar (10 in WG)

Max 45 mbar (18 in WG)

 

 

 

 

 

 

 

 

 

 

 

 

Main Burner Gas Pressure

mbar

4.2

3.3

4.6

 

4.8

7.5

5.8

7.8

12.0

7.6

Start Gas Pressure

mbar

NA

NA

NA

 

1.6

2.5

0.8

1.0

1.5

3.1

Gas Rate

(m3/h)

2.1

2.8

3.5

 

4.9

6.1

7.8

9.1

10.4

13.1

(kg/h)

3.9

5.1

6.5

 

9.1

11.3

14.5

16.9

19.2

24.3

 

 

Start Gas Orifice

(mm dia)

 

 

 

 

5.0

6.0

7.0

7.0

7.0

 

Main Gas Orifice

(mm dia)

8.5

10.0

10.0

 

14.5

14.5

14.5

14.5

14.5

 

Burner Type

 

AZUR

BLU

BLU

 

BLU

BLU

BLU

BLU

BLU

BLU

 

60 AH

120 AH

120 AH

 

170 AH

250R AH

250 AH

250 AH

250S AH

350 AH

 

 

 

Burner Head

 

S

S

S

 

S

S

S

S

S

LPG

Burner Head Setting

(mm)

0

10

13

 

15

14

24

24

24

20

Air Setting

 

3.0

4.8

6.6

 

2.6

4.5

3.1

4.2

1.6

1.8

Valve Type Main Gas

 

 

MBDLE

 

 

MBDLE

 

MBDLE

 

MBDLE

 

 

405

 

 

407

 

410

 

412

 

 

 

 

 

 

 

Valve Type Start Gas

 

 

NA

 

 

 

 

S.I.T. 0 832 051

 

 

NOTE: For adjustment of head setting, see Ecoflam Instructions

8

Page 14
Image 14
Roberts Gorden POP-ECA/PGP-ECA 015 to 0100 service manual Model, Max 25 mbar 10 in WG, Max 45 mbar 18 in WG