14.2 Troubleshooting for Oil Burners (see manufacture’s instructions)

COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL

14.2 Troubleshooting for Oil Burners (see manufacture’s instructions)

WARNING

START

Assuming fuel & electrical

supplies are ON

Electrical Shock Hazard Do not touch ignition components.

Voltage from ignition components is high.

Failure to follow these instructions can result in death or electrical shock.

Does the burner fire?

No

Yes

Does the burner control

box 'lockout' before 15 Yes seconds?

No

Check if the control fuse in

the heater has blown.

Yes

Disconnect photo cell

and try again.

Yes

Use Section 14.4 to

trace fault.

No

Check supply to burner

No

Check control box.

motor.

 

 

 

 

 

Yes

 

No

 

 

 

Repair or replace.

No

Control box faulty.

Repair or replace.

 

Does the burner control

box 'lockout' after 15 Yes seconds?

No

Heater Operating

TROUBLESHOOT ENDS. No

 

 

Check ignition electrodes are

Did the burner fire?

No

set as in the manufacturer's

instructions, the fuel supply

 

 

 

 

and nozzle.

Yes

 

No

Use Section 14.4 to

 

Check oil solenoid valve.

trace fault.

 

 

 

If problems persist, contact ROBERTS GORDON® at Tel: +44 (0)121 506 7709 www.rg-inc.com

For your safety and optimum heater performance, use only ROBERTS GORDON® replacement parts.

Conduct Commissioning procedure as shown on Page 33, Section 10.