Page 58
Image 58
5.Check the correct rotation of the fan as on Page 33, Section 10.1.5.

COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL

5.Check the correct rotation of the fan as on Page 33, Section 10.1.5.

NOTE: The direct drive fan unit motor can only be replaced as a complete fan/motor assembly.

Figure 22: Combination Fan/Limit Thermostat

Figure 22: Combination Fan/Limit Thermostat WARNING

Fire Hazard

Break-off link must be removed from replacement thermostat.

Heat exchanger damage may result.

Failure to follow these instructions can result in death, injury, property damage or product damage.

Set Point 3 Limit Temp.

Set Point 2 Fan On

Set Point 1 Fan Off

Fan Terminals

Manual Fan Switch

(White)

Pull out for normal operation. Push in for continuous fan.

Dial

Push Screwdriver in and hold to release

Push in Lock

Wire to Controlled Equipment

Limit Stat

Manual Reset Button (Red)

Limit Terminals

ROBERTS GORDON®

BREAK- FF LI K thermostatsMUST BEdo REMOVEDnot have a

break-off link. Remove break-off link if thermostat was not provided by Roberts-Gordon.

52