14.3 Troubleshooting for Gas Burners (see manufacturer’s instructions)

SECTION 14: TROUBLESHOOTING

14.3 Troubleshooting for Gas Burners (see manufacturer’s instructions)

START

Assuming fuel & electrical

supplies are ON.

 

Is the pressure switch

 

Does the burner fan run? No

at rest?

No

(no contact open)

 

 

TROUBLESHOOT ENDS. WARNING

Electrical Shock Hazard Do not touch ignition components.

Voltage from ignition components is high.

Failure to follow these instructions can result in death or electrical shock.

See Section 10.5.1 for

setting.

Yes

Fault lies elsewhere.

Yes

Does the burner control box 'lockout' before 10 seconds?

No

Does the burner control box 'lockout' after 10 seconds?

No

Does the burner fire?

 

Use Section 14.4 to check

 

 

Yes

the flame

 

 

 

monitoring system.

 

 

 

Check settings

 

Check combustion air fan is

Yes

No

clean. Check combustion

pressure switches.

chamber is clean and sound.

 

 

 

 

 

Check flue is clean and

 

 

 

sound. Check joint between

 

 

 

flue spigot and flue is sound.

 

Check ignition circuit, fuel

 

 

No

supply and gas solenoid

 

 

 

valves.

 

 

Yes

Use Section 14.4 to check

Does 'lockout' occur? Yesthe flame monitoring system.

No

 

 

Does main gas fire?

No

Check main gas valves and

wiring.

 

 

Yes

 

 

Heater Operating

 

If problems persist, contact

No

ROBERTS GORDON® at

TROUBLESHOOT ENDS.

Tel: +44 (0)121 506 7709

 

 

 

www.rg-inc.com

47