Samsung AF28FSSDADFNFA Performing leak test, Test part for indoor unit, English, 1 Nm = 10 kgfcm

Models: AF28FSSDADFNMG AF28FSSDADFNFA

1 54
Download 54 pages 46 Kb
Page 52
Image 52
Performing leak test

Performing leak test

ffUse leak tester or soapsuds on the pipe connection part after performing vacuum pump.

Check for

Check for

leakage

 

leakage

Test part for indoor unit

Test part for outdoor unit

ffBefore inspecting the leakage, use a torque wrench to close the cap for the service valve.(Comply with a tightening torque for each size of the diameter, and tighten the cap firmly to prevent any leakage.)

ffTo check for any possible leakage, insert inert gas into the pipes connected to indoor/outdoor units and check the connection part of the indoor/outdoor units with soap lather or liquid for leakage test.

ENGLISHTest part for indoor unit

Tightening torque for body cap (Refer to the table)

Spindle

Charging OuterTightening torque❋❋1 N•m = 10 kgf•cm core Manual backgroundManual background

R-22: Diameter of the screw - 7/16-20UNF

R-410A: Diameter of the screw - 1/2-20UNF

Tightening torque for charging port cap (Refer to the table)

Outer

Tightening torque

 

 

Diameter

Body cap

Charging port

(mm)

(N•m)

cap (N•m)

 

 

 

Ø6.35

20 ~ 25

 

Ø9.52

20 ~ 25

 

Ø12.7

25 ~ 30

10 ~ 12

Ø15.88

30 ~ 35

 

Ø19.05

35 ~ 40

 

❋❋1 N•m = 10 kgf•cm

51