| LED11 | LED5 LED6 |
|
| ||
|
|
| LED10 |
|
|
|
|
| |
|
|
|
|
|
| LED7 |
|
| |
|
|
| ① |
|
| LED8 |
|
| |
|
|
|
|
|
|
|
| ||
|
|
| LED4 |
|
| LED12 |
|
| |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| ② |
|
| |
|
|
|
|
|
| LED9 |
|
| |
|
|
| LED0 LED1 | LED2 | LED3 | ③ |
|
| |
|
|
|
|
|
| ||||
No. |
| Label |
|
| Functions |
| Fast | ||
| Status display | Lit | Not lit | Slow blink | |||||
|
|
| blink | ||||||
LED0 |
| INPUT | Input power status | Normal input |
| Input error | |||
| - | - | |||||||
LED1 | OUTPUT | UPS output power status Inverter operation | OFF | Bypass operation | - | ||||
LED2 | ECONOMY | Operation mode | Economy mode | OFF (*3) | - | - | |||
operation | (*1) |
| |||||||
|
|
|
|
|
|
| |||
LED3 |
| DOUBLE | Operation mode | Double conversion | OFF (*3) | - | - | ||
CONVERSION | mode operation (*2) | ||||||||
LED4 | BATT.LOW | Battery status | Battery power low | Battery power | Battery exhausted | - | |||
normal |
| ||||||||
|
|
| Load level 25% |
|
|
|
| ||
|
|
| Load 25% or more | Load under 25% | - | - | |||
LED5 |
| 25 | Output voltage setting | - | Setting other than | 100V setting (*4) | - | ||
|
|
| 100V (*4) | 100V | |||||
LED6 | LOADLEVEL(%) | 50 | Load level 50% | Load 50% or more | Load under 50% | - | - | ||
Output voltage setting | - | Setting other than | 110V setting (*4) | - | |||||
|
|
| 110V (*4) | 110V | |||||
|
|
|
|
|
|
| |||
LED7 |
| 75 | Load level 75% | Load 75% or more | Load under 75% | - | - | ||
| Output voltage setting | - | Setting other than | 115V setting (*4) | - | ||||
|
|
| 115V (*4) | 115V | |||||
|
|
|
|
|
|
| |||
LED8 |
| 100 | Load level 100% | Load 100% or more | Load under 100% | - | - | ||
| Output voltage setting | - | Setting other than | 120V setting (*4) | - | ||||
|
|
| 120V (*4) | 120V | |||||
|
|
|
|
|
|
| |||
LED9 |
| O.L. | Overload display | Load 105% or more | Load under 105% | None | - | ||
LED10 |
| ALARM | Alarm display | Failure detected | No failure | - | - | ||
① |
| INV.ON | Inverter operation On/Off operation |
|
|
|
| ||
STAND BY |
|
|
|
| |||||
LED11 |
| INV.ON | Inverter operation status | Inverter operation | Off | Bypass operation | - | ||
STAND BY | |||||||||
② | BATT.TEST | Battery test |
|
|
|
|
| ||
LED12 | BATT.TEST | Battery test | Result: Normal | - | Result: Error | Status: | |||
Testing | |||||||||
|
| CLEAR | Stop buzzer, clear result of battery test |
|
| ||||
③ |
|
|
|
|
※1. Economy mode operation・・・・When power conditions are good, UPS supplies this power to the load.
※2. Double conversion mode operation・・・・When power conditions fluctuate, UPS converts to the stable power, and supplies to the load.
※3. Active Filter Mode operation・・・・When load power fluctuates. Suppresses high frequencies generated by the load and improves power factor.
When the green DOUBLE CONVERSION and the green ECONOMY are both off, the UPS is in Active Filter Mode. ※4. The output voltage setting is displayed for about 5 seconds after the UPS is powered on (LED initialization display).
This manual uses a frame |
| to indicate switches. (Example: | INV.ON/STAND BY | ). |
It also describes the color of the LED whenever it refers to an indicator on the control panel. (Examples: Green INV.ON/STAND BY, red ALARM)
: Indicates a lit LED
In the illustrations in this manual
: Indicates a blinking LED
− 10 −