10.User Settings

10.1Setup Menu Item List

You can configure the UPS by setting the menu items in the following list. Configure it according to your environment and requirements.

The controls and indicators on the control panel are used to set items in the Setup menu. For details, see §10.2 “Setup Menu Operations”.

Whenever you change a menu item setting, we recommend that you place a check mark in the “Current Setting” field of the Setup Menu Item List.

LED blinks LED off

No.

Menu Item

Item Selection

Setting

Item Setting

Default

Current

 

Description

 

 

Notes

 

 

 

LEDs

LEDs

Setting

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto

● ○ ○ ○

*

 

Switch the UPS operating mode

automatically.

UPS operation mode

Double Conversion

○ ● ○ ○

 

 

Set the UPS operating mode to Double Conversion mode.

● ○ ○ ○

Economy

 

 

 

Set the UPS operating mode to Economy mode.

 

 

 

● ● ○ ○

 

 

However, the mode of UPS might change into the “Double Conversion”

 

 

 

 

 

 

 

mode depending on the condition of the input potential and the load.

 

 

 

100V

● ○ ○ ○

 

 

100V setting

 

Set the rated output voltage.

 

Output voltage

110V

○ ● ○ ○

 

 

110V setting

 

The case of E11A202U001

 

 

 

Please do not change setting the voltage.

(RESTART)

○ ● ○ ○

115V

● ● ○ ○

 

 

115V setting

 

 

 

 

 

And use UPS as 120V setting.

 

 

 

120V

○ ○ ● ○

*

 

120V setting

 

(For UL rules)

 

Frequency sync range

 

1%

● ○ ○ ○

 

 

±1% allowance

 

Set the range (%) over which the output

3%

○ ● ○ ○

*

 

±3% allowance

 

frequency is adjusted to variations in the

 

 

 

 

(RESTART)

● ● ○ ○

5%

● ● ○ ○

 

 

±5% allowance

 

input frequency in Economy Mode and

 

 

 

 

 

 

Active Filter Mode.

 

Battery startup

50Hz

● ○ ○ ○

 

 

50Hz setting

 

Set the inverter output frequency when

frequency

 

 

 

 

 

 

 

 

UPS restarts from the batteries from

 

○ ○ ● ○

60Hz

○ ● ○ ○

*

 

60Hz setting

 

stopped status.

 

 

 

 

 

 

 

 

Do not use this setting.

● ○ ○ ○

 

 

 

 

 

 

 

 

Workstation

○ ● ○ ○

*

 

Setting for communications by the power management software over serial

PC Interface mode

 

or LAN connection.

 

 

 

● ○ ● ○

 

 

 

 

 

 

 

 

 

Serial Login

● ● ○ ○

 

 

Shutdown by serial login.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not use this setting.

○ ○ ● ○

 

 

 

 

 

 

 

Serial baud rate

9600

● ○ ○ ○

*

 

Set the baud rate to 9600 bps.

Set the communications baud rate when

4800

○ ● ○ ○

 

 

Set the baud rate to 4800 bps.

a workstation, PC, or optional LAN card

○ ● ● ○

 

 

 

 

 

2400

● ● ○ ○

 

 

Set the baud rate to 2400 bps.

is connected.

 

 

 

Auto

● ○ ○ ○

*

 

Auto restart

 

Specify when to restart the UPS after a

 

 

 

OFF

○ ● ○ ○

 

 

The UPS stays off.

 

 

Restart time

 

30%

● ● ○ ○

 

 

Same

behavior as Auto

when

power outage and shutdown of the UPS

 

 

battery charge reaches 30%.

 

due to final discharge of the batteries.

 

 

 

 

(battery charge rate)

● ● ● ○

50%

○ ○ ● ○

 

 

Same

behavior as Auto

when

When 30%, 50%, or 80% is selected, the

 

 

 

 

 

battery charge reaches 50%.

 

UPS does not restart until the batteries

 

 

 

 

 

 

 

 

 

 

80%

● ○ ● ○

 

 

Same

behavior as Auto

when

are charged to the specified level.

 

 

 

 

 

battery charge reaches 80%.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All patterns

● ○ ○ ○

*

 

All sounds

 

 

 

Buzzer sound

Patterns 1

○ ● ○ ○

 

 

Do not emit sounds on power outage, battery test, and overload.

○ ○ ○ ●

Pattern 2

● ● ○ ○

 

 

Emit alarm and key click sounds.

 

 

 

 

 

 

 

 

 

 

 

 

○ ○ ● ○

 

 

Emit key click sounds only.

 

 

 

 

 

 

1 second

● ○ ○ ○

*

 

Turn inverter off when pressed for 1 second.

Set the response time for

 

 

 

 

 

 

 

 

 

 

 

switch press to stop inverter

 

 

 

3 seconds

○ ● ○ ○

 

 

Turn inverter off when pressed for 3 seconds.

switch

 

 

power supply.

 

response time

● ○ ○ ●

Special operation

 

 

 

Turn inverter off on special operation. Select

this setting to keep the

 

 

● ● ○ ○

 

 

inverter from being turned off by an accidental operation. See §9.4 "UPS

 

 

 

 

 

 

 

 

 

 

 

 

Shutdown (Daily)" for operation details.

 

 

Overload recovery

 

Auto return

● ○ ○ ○

*

 

Auto recovery with time

 

Set the conditions for automatic switch

 

 

back to inverter power supply (auto

 

 

 

 

 

 

 

operation

○ ● ○ ●

Bypass

○ ● ○ ○

 

 

Fixed as bypass on overload

 

return) after switching to bypass power

 

 

 

 

 

 

 

 

 

 

supply because of overload.

 

 

 

 

 

 

 

 

 

 

 

Inverter stop

OFF

● ○ ○ ○

*

 

The UPS stays off.

 

Specify the UPS operation during

 

 

 

Operation (RESTART)

● ● ○ ●

Bypass

○ ● ○ ○

 

 

Switch to bypass operation when

inverter power supply stops.

 

 

 

 

 

 

 

inverter stops.

 

 

 

 

 

 

Battery voltage level

● ○ ○ ○

*

 

When low battery voltage level is

 

 

 

Low battery voltage

 

 

detected.

 

 

 

2 minutes

○ ● ○ ○

 

 

When remaining battery capacity

Specify the timing for triggering the low

signal timing

○ ○ ● ●

 

 

is 2 minutes.

 

battery voltage signal.

 

 

 

3 minutes

● ● ○ ○

 

 

When remaining battery capacity

 

 

 

 

 

 

 

is 3 minutes.

 

 

 

 

 

 

5 minutes

● ○ ○ ○

*

 

5 minutes backup

 

Set the UPS backup time on power

 

 

 

20 minutes

○ ● ○ ○

 

 

20 minutes backup

 

 

 

 

 

 

 

outage.

 

 

 

 

30 minutes

● ● ○ ○

 

 

30 minutes backup

 

 

 

Battery backup time

 

 

 

 

An external battery must be connected

40 minutes

○ ○ ● ○

 

 

40 minutes backup

 

for settings of 20 minutes or higher.

(RESTART)

● ○ ● ●

60 minutes

● ○ ● ○

 

 

60 minutes backup

 

These external battery accommodate by

 

 

 

 

 

 

 

 

 

 

Technical Service Personnel.Ask for

 

 

 

90 minutes

○ ● ● ○

 

 

90 minutes backup

 

 

 

 

 

 

 

Tehnical Service Personnel.

 

 

 

120 minutes

● ● ● ○

 

 

120 minutes backup

 

 

 

 

 

 

 

Do not use another setting.

 

 

 

180 minutes

○ ○ ○ ●

 

 

180 minutes backup

 

 

 

 

Battery type

 

● ○ ○ ○

 

 

5-year lifetime type

 

Set the battery type.

10 year

○ ● ○ ○

 

 

10-year lifetime type

 

Set this when you exchange the battery

(RESTART)

○ ● ● ●

 

 

 

 

 

 

3 year

● ● ○ ○

 

 

3-year lifetime type

 

or connect an external battery.

 

 

 

180 days

● ○ ○ ○

*

 

Check batteries every 180 days.

Set the interval (number of days) for the

Battery check schedule

90 days

○ ● ○ ○

 

 

Check batteries every 90 days.

automatic battery check. The check is

● ● ● ●

30 days

● ● ○ ○

 

 

Check batteries every 30 days.

carried out automatically when the

 

 

 

 

 

 

 

None

○ ○ ● ○

 

 

No battery check.

 

specified number of days has elapsed.

 

Reset remaining

Do not reset

● ○ ○ ○

*

 

Do not reset.

 

 

 

 

 

 

 

Reset the battery information (remaining life, accumulated battery

 

battery life

○ ○ ○ ○

Reset

○ ● ○ ○

 

 

operating time, number of power outages, LED remaining life display),

 

 

 

 

 

 

 

when you exchange the battery.

 

 

23