6. Installation
・When installing the UPS, carefully follow the instructions in this Instruction Manual.
・Install the UPS on a stable surface that can bear the weight (29 kg, 63.93 lbs).
This surface should be flat, so the UPS cannot fall and cause bodily injury.
・The possibility of vibration and shock should be minimized at the installation location.
・All work that involves lifting the UPS, such as mounting it in a rack or attaching the stand, should be carried out by at least 2 persons.
CAUTION ・ Be careful to avoid straining your lower back when moving and installing the UPS. ・ There is a danger that the UPS could fall or be dropped during relocation or
installation. Always hold the UPS securely by the upper edges. Failure to do so can result in bodily injury or damage to the UPS.
6.1 EnvironmentDo not install the UPS in the following locations:•Where the ambient temperature exceeds 40°C (104°F).For optimum battery life, install the UPS where the ambient temperature remains between 20 to 25°C (68 to 77°F).
•Where high humidity may occur.•Where corrosive gas or salt spray may be present.•Where it may be subject to vibration and shock.•Where dust may accumulate.•In a poorly ventilated rack (when the UPS is rack mounted).6.2 Transporting |
|
| When moving the UPS, do not let it tilt |
|
|
| more than 10 degrees to either side. |
Transport the UPS in its original packing |
| ||
carton, removing it only when near the |
| Tilting of more than 10 degrees can | |
| cause the UPS to fall, resulting in | ||
installation location. |
| ||
CAUTION | bodily injury. | ||
|
|
| If you must tilt the UPS more than 10 |
6.3 Installation Space |
|
| degrees, be careful not to let it fall. |
|
|
|
|
•At least 1 meter (about 40 inches) at the front and 50 cm (about 20 inches) at the back for maintenance when needed.
•At least 1 meter (about 40 inches) from CRT displays to allow for slight leakage of magnetic flux. Allow some space from devices which might be affected by magnetic flux.
Installation Space for Vertical or Horizontal Installation
Exhaust spac
At least 50 cm (20 in)
Maintenance space
Exhaust space At least
20cm (8 in)
(Back)
E11A
△
At least Front 20cm (8 in)
Intake space
Maintenance space
At least 1m (40 in)
Installation Space for Rack Mounting
Maintenance space
At least 50 cm (20 in)
Exhaust space
At least 20cm
(8 in)
(Back)
The rack that
E11Athere are ventilation
holes in the door is
(Front) recommended.
Intake space |
| |
At least 20cm |
| |
Rack | ||
(8 in) | ||
| ||
Maintenance space |
| |
At least 1m (40 in) |
|