6. Installation

When installing the UPS, carefully follow the instructions in this Instruction Manual.

Install the UPS on a stable surface that can bear the weight (29 kg, 63.93 lbs).

This surface should be flat, so the UPS cannot fall and cause bodily injury.

The possibility of vibration and shock should be minimized at the installation location.

All work that involves lifting the UPS, such as mounting it in a rack or attaching the stand, should be carried out by at least 2 persons.

CAUTION Be careful to avoid straining your lower back when moving and installing the UPS. There is a danger that the UPS could fall or be dropped during relocation or

installation. Always hold the UPS securely by the upper edges. Failure to do so can result in bodily injury or damage to the UPS.

6.1 EnvironmentDo not install the UPS in the following locations:Where the ambient temperature exceeds 40°C (104°F).

For optimum battery life, install the UPS where the ambient temperature remains between 20 to 25°C (68 to 77°F).

Where high humidity may occur.Where corrosive gas or salt spray may be present.Where it may be subject to vibration and shock.Where dust may accumulate.In a poorly ventilated rack (when the UPS is rack mounted).
6.2 Transporting

 

 

When moving the UPS, do not let it tilt

 

 

 

more than 10 degrees to either side.

Transport the UPS in its original packing

 

carton, removing it only when near the

 

Tilting of more than 10 degrees can

 

cause the UPS to fall, resulting in

installation location.

 

CAUTION

bodily injury.

 

 

 

If you must tilt the UPS more than 10

6.3 Installation Space

 

 

degrees, be careful not to let it fall.

 

 

 

 

During installation, provide the following space around the UPS.At least 20 cm (about 8 inches) at the front as air intake space for cooling.At least 20 cm (about 8 inches) at the back as air exhaust space for cooling

At least 1 meter (about 40 inches) at the front and 50 cm (about 20 inches) at the back for maintenance when needed.

At least 1 meter (about 40 inches) from CRT displays to allow for slight leakage of magnetic flux. Allow some space from devices which might be affected by magnetic flux.

Installation Space for Vertical or Horizontal Installation

Exhaust spac

At least 50 cm (20 in)

Maintenance space

Exhaust space At least

20cm (8 in)

(Back)

E11A

At least Front 20cm (8 in)

Intake space

Maintenance space

At least 1m (40 in)

Installation Space for Rack Mounting

Maintenance space

At least 50 cm (20 in)

Exhaust space

At least 20cm

(8 in)

(Back)

The rack that

E11Athere are ventilation

holes in the door is

(Front) recommended.

Intake space

 

At least 20cm

 

Rack

(8 in)

 

Maintenance space

 

At least 1m (40 in)

 