| Condition |
|
|
|
|
|
| Countermeasure |
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
| No recovery from utility |
|
| ・ Check whether | MAIN MCCB |
| on the back panel of the UPS is in the |
| |||||
|
|
| “ON” position. (If |
| MAIN MCCB |
|
| is set to the “OFF” position during |
| ||||
| power source failure. |
|
| normal operation, | the same operation as for a utility power source failure |
| |||||||
| Utility power source |
|
| will be triggered.) See §9.1 “UPS Startup (Normal Operation)”. |
| ||||||||
| failure occurs frequently. |
|
| ・ Verify that input voltage and input frequency are within the rated limits. |
| ||||||||
|
|
|
| See §15.3 “Specifications”. |
|
|
|
| |||||
|
|
|
| ・ UPS automatically shifts to a double conversion when the operation mode |
| ||||||||
|
|
|
| of UPS is set by economy by the following conditions. |
| ||||||||
|
|
|
| “When UPS is operated by about ratings (The display of “LOAD |
| ||||||||
|
|
|
| LEVEL(%)” shows the state of about 75 or more.), and the quality of the |
| ||||||||
|
|
|
| input power supply worsens continuously or momentary.” |
| ||||||||
| UPS is operated in the |
|
| After the mode of UPS has shifted to "Double Conversion" once,.the mode |
| ||||||||
|
|
| does not return to "Economy" even if the quality of the input power |
| |||||||||
| “Double Conversion” mode |
|
|
| |||||||||
|
|
| improves to cleanness. |
|
|
|
| ||||||
| though set UPS in the |
|
|
|
|
|
| ||||||
|
|
| In this case, it is necessary to reduce the load of UPS. |
| |||||||||
| Economy” mode. |
|
|
| |||||||||
|
|
| (The display of "LOAD LEVEL(%)" is roughly a state below "75".) |
| |||||||||
|
|
|
|
| |||||||||
|
|
|
| UPS is not abnormal . However, it is necessary to reduce the load of UPS to |
| ||||||||
|
|
|
| return the mode to "Economy". |
|
|
|
| |||||
|
|
|
| Moreover, it is necessary to adjust the load so that the display of "LOAD |
| ||||||||
|
|
|
| LEVEL(%)" should not exceed "75" to operate UPS only in the economy |
| ||||||||
|
|
|
| mode. |
|
|
|
|
|
|
| ||
|
|
|
| ・ Check whether the |
| Forced Bypass | switch is set to “Inverter”. This |
| |||||
|
|
|
| switch is located inside the front panel of the unit. Remove the front panel |
| ||||||||
|
|
|
| to check. |
|
|
|
|
|
|
| ||
|
|
|
| See 14 “Maintenance Bypass Power Supply (Option)”. |
| ||||||||
| UPS does not switch from |
|
| ・ When item ⑩ “Overload recovery operation” in §10.1 “Setup Menu Item |
| ||||||||
|
|
| List” is set to “Auto return”: The UPS switches to inverter operation every |
| |||||||||
| bypass operation to |
|
| 2.5 seconds, and switches back to bypass power supply if the overload |
| ||||||||
| normal operation. |
|
| condition still persists. This cycle is repeated. |
| ||||||||
|
|
|
| ・ When item ⑩ “Overload recovery operation” in §10.1 “Setup Menu Item |
| ||||||||
|
|
|
| List” is set to “Bypass”: If the utility power voltage is low and the load |
| ||||||||
|
|
|
| current is below the overload detection threshold when the UPS switches |
| ||||||||
|
|
|
| to bypass power supply, the UPS continues to switch between inverter |
| ||||||||
|
|
|
| power supply and bypass power supply. |
| ||||||||
|
|
|
| ・ A battery test cannot be performed when: |
| ||||||||
|
|
|
| ① Inverter is stopped. |
|
|
|
| |||||
| Cannot perform battery |
|
| ② Bypass power supply is active. |
| ||||||||
| test. |
|
| ③ Input voltage or input frequency is out of range. |
| ||||||||
|
|
|
| ④ Shutdown under remote control is in progress. |
| ||||||||
|
|
|
| ⑤ Equipment is defective. |
|
|
|
| |||||
|
|
|
|
|
| ||||||||
|
|
|
| ・ Verify that item ⑤ “PC Interface mode” in §10.1 “Setup Menu Item List” |
| ||||||||
| Serial communication |
|
| is set to “Workstation”. Check the serial connection. See §5.3 “External |
| ||||||||
|
|
| Interfaces”. |
|
|
|
|
|
|
| |||
| fails. |
|
|
|
|
|
|
|
|
| |||
|
|
| ・ Check the setting of item ⑥ “Serial baud rate” in §10.1 “Setup Menu Item |
| |||||||||
|
|
|
|
| |||||||||
|
|
|
| List”. The factory default setting of this item is “9600”. |
| ||||||||
|
|
|
|
|
| ||||||||
| Automatic inverter restart |
|
| ・ Check the setting of item ⑦ “Restart time (battery charge rate)” in §10.1 |
| ||||||||
|
|
| “Setup Menu Item List”. Automatic inverter restart does not occur if this |
| |||||||||
| does not occur after |
|
|
| |||||||||
|
|
| item is set to “OFF”. |
|
|
|
| ||||||
| shutdown due to battery |
|
|
|
|
|
| ||||||
|
|
| If this item is set to “30%”, “50%”, or “80%”, the UPS does not start until |
| |||||||||
| exhaustion following |
|
|
| |||||||||
|
|
| the batteries are charged to the specified level. |
| |||||||||
| power outage. |
|
|
| |||||||||
|
|
| The factory default setting of this item is “Auto”. |
| |||||||||
|
|
|
|
| |||||||||
| Green DOUBLE |
|
| ・ The UPS is switching frequently between operating modes because the |
| ||||||||
| CONVERSION and green |
|
| utility power is unstable. Set the UPS operating mode to “Double |
| ||||||||
| ECONOMY light and go |
|
| Conversion Mode”. For details, see item ① “UPS operation mode” in §10.1 |
| ||||||||
| off frequently at irregular |
|
| “Setup Menu Item List”. |
|
|
|
| |||||
| intervals. |
|
| The factory default setting of this item is “Auto”. |
|
− 33 −