7. Wiring

 

Check that input and output power plugs are firmly seated. Do not exceed the

 

rated capacity when connecting loads to the output terminals. Check that

 

plugs and cards are firmly seated in the external interfaces. Failure to observe

CAUTION

these precautions can result in electric shock, fire, or bodily injury.

The input power plug must be grounded. Failure to ground it can result in

 

electric shock.

7.1 UPS WiringCheck that MAIN MCCB is in the “OFF” position.Connect the INPUT power plug of the UPS to a utility power outlet.

 

 

 

 

This figure shows E11A202U001.

 

 

 

 

As for E11A202U001J, shape and

Switch is “OFF.

 

 

the number of receptacles are

 

 

 

 

different.

 

 

 

 

To 3-prong grounded

 

 

 

 

utility power outlet

 

 

 

 

Length: at least 1.8 m

 

 

 

 

(at least 7.09 inches)

MODEL

Type of Input pulg

 

Note

 

NEMA TYPE 5-20P

R

 

When the AC input power is single-wire

 

(seen from prong side)

 

E11A202U001

 

(Or, N)

grounded, always connect the ground

 

 

 

phase to the S terminal (phase) side on

 

 

 

 

 

 

E

 

the UPS.

 

 

 

 

 

NEMA TYPE L5-30P

 

S(W)

When the AC input power is single-wire

 

(seen from prong side)

 

 

 

(Or, N)

E11A202U001J

 

 

grounded, always connect the ground

 

 

 

 

 

 

phase to the S terminal (phase) side on

 

 

 

 

Ethe UPS.

16