2. For Proper Operation
(1) Please use UPS as a commercial power supply in the region and the output voltage of UPS are matched referring to the table below.
MODEL | AC input voltage | AC input frequency | NOTE | |
E11A202U001 | 120V | 50 or 60Hz (±5%) | ※ | |
E11A202U001J | 100,110,115,120V | 50 or 60Hz (±5%) | ※ |
※ The frequency variation range is set to ±3% when the UPS is shipped from the factory.
If the frequency variation range of input power supply is ±5%, select ±5% as described in item ③ “Frequency sync range” of §10.1 “Setup Menu Item List”. An input power error occurs when the frequency sync range exceeds the setting value, preventing the UPS from switching to inverter operation.
(2) The current capacity of the AC power supply must satisfy the requirements of the UPS (It is different depending on the model.)
MODEL | Input capacity | Recommended capacity of breaker |
E11A202U001 | 1.8kVA | 20A or more (Demand of UL rules) |
|
|
|
E11A202U001J | 1.8kVA | 30A or more (Demand of UL rules) * |
*NOTE: Please set up Branch circuit protector of 30A in the switchboard for E11A202U001J. In branch circuit protector, please protect two poles of the ac input. (Demand of UL rules)
2.2Installation Precautions*Installation must be in accordance with the National Electric Code Articles
(1)Carefully consider the leakage current when a leakage circuit breaker is installed on the input side. The maximum leakage current of the UPS is 3mA.
(2)Keep the UPS at least 1 m (about 40 inches) away from CRT displays. Other devices which may be sensitive to magnetic flux should be kept away from the UPS, as it emits a slight amount of magnetic flux.
(3)The UPS employs a fan for
When mounting the UPS in a rack, use a rack which allows ventilation and provide at least 20 cm (about 8 inches) clearance from the front and back of the rack to permit free airflow at the air intake and exhaust vents. Also, for maintenance purposes, a space of at least 1 m (about 40 inches) will be needed at the front of the rack, and a space of at least 50 cm (about 20 inches) will be needed at the back of the rack.
For details, see §6.3 “Installation Space”.(4)When the AC input power is
(5)As far as possible, do not ground the output (load) side. If you must make a
(1)Never
Do not connect laser printers, plain paper fax machines, copy machines, or overhead projectors as load devices. Such devices typically include heating elements that draw high current. This may cause an overload that could prevent battery backup operation when an outage occurs, and could damage the UPS.
−6 −