・Wear insulated gloves and take other precautions when connecting the batteries. Otherwise electric shock can result.
・There is a constant voltage (max. approx. 48V: approx. 12V ⋅ 4) at the battery terminals. Do not touch them with your hands or short circuit them. Bodily injury can result.
CAUTION | ・ The battery connector cannot be inserted in the wrong orientation. If it does not go |
| in, do not try to force it. Doing so can damage the connector and result in electric |
| shock. |
| ・ Be careful not to get your hands caught when securing the cover. |
Connect the battery connectors inside the front cover before installation of the UPS. Proceed as follows to connect the battery connectors.
①Remove the front panel of the UPS.②Remove the screw on the right side of the battery cover, and then remove the battery
cover.③Remove the insulation tape from the battery connecter of the battery pack side.
④ Connect the battery connector.④The connector cannot be inserted
in the wrong orientation. Push in until you hear a click.
① Remove by sliding in the direction | ② Remove 1 screw, and remove |
of the arrow while firmly pressing | the battery cover by sliding in |
the two locations indicated by ● | the direction of the arrow. |
| Do not lose the removed screw. |
⑥ Attach the battery cover and fix this cover with 1 screw. ⑦ Attach the front panel.
⑥ Slide the cover in and secure | ⑤ Confirm the switch of "Forced Bypass" is | |
on "Inverter" side. | ||
with the screw on the right side. | ||
|
⑦First catch the claws
on the right side, then push the left side in.
This completes the battery connector connection.