9. Operating Procedures
9.1 UPS Startup (Normal Operation)
① Set MAIN MCCB on the back panel of the UPS to “ON”.
①Set to “ON”.
LEDs | Blinking |
Green INPUT | |
Green INV.ON/STAND BY | Off |
Green OUTPUT | Off |
↓ |
|
Green INPUT | Lit |
Green INV.ON/STAND BY | Off |
Green OUTPUT | Off |
Check that the INPUT indicator has changed from blinking to lit, and then proceed to step ②.
②Press and hold for one second.
| Buzzer |
| |
| Musical trill |
| |
Hold for 1 second. | LEDs |
| |
Green INPUT | Lit | ||
| |||
| Green INV.ON/STAND BY | Lit | |
| Green OUTPUT | Lit |
・The green LOADLEVEL 25 to 100% indicator and the red LOADLEVEL O.L indicator light according to the load connected to the UPS.
・The green ECONOMY indicator lights when the UPS operating mode is Economy Mode.
・The green DOUBLE CONVERSION indicator when the UPS operating mode is Double Conversion Mode.
・When the green DOUBLE CONVERSION indicator and the green ECONOMY indicator are both off, the UPS is in Active Filter Mode.
This manual uses a frame |
| to indicate switches. (Example: | INV.ON/STAND BY | ). |
It also describes the color of the LED whenever it refers to an indicator on the control panel. (Examples: Green INV.ON/STAND BY, red ALARM)
Indicates a lit LED
In the illustrations in this manual
Indicates a blinking LED
− 19 −