9. Operating Procedures

9.1 UPS Startup (Normal Operation)

Set MAIN MCCB on the back panel of the UPS to “ON”.

Set to “ON”.

LEDs

Blinking

Green INPUT

Green INV.ON/STAND BY

Off

Green OUTPUT

Off

 

Green INPUT

Lit

Green INV.ON/STAND BY

Off

Green OUTPUT

Off

Check that the INPUT indicator has changed from blinking to lit, and then proceed to step .

Press and hold for one second.

 

Buzzer

 

 

Musical trill

 

Hold for 1 second.

LEDs

 

Green INPUT

Lit

 

 

Green INV.ON/STAND BY

Lit

 

Green OUTPUT

Lit

The green LOADLEVEL 25 to 100% indicator and the red LOADLEVEL O.L indicator light according to the load connected to the UPS.

The green ECONOMY indicator lights when the UPS operating mode is Economy Mode.

The green DOUBLE CONVERSION indicator when the UPS operating mode is Double Conversion Mode.

When the green DOUBLE CONVERSION indicator and the green ECONOMY indicator are both off, the UPS is in Active Filter Mode.

This manual uses a frame

 

to indicate switches. (Example:

INV.ON/STAND BY

).

It also describes the color of the LED whenever it refers to an indicator on the control panel. (Examples: Green INV.ON/STAND BY, red ALARM)

Indicates a lit LED

In the illustrations in this manual

Indicates a blinking LED

19