PowerLogicTM Series EM4000 |
|
Installation Guide | 11/2013 |
|
|
For a 208Y/120V
•Connect meter terminal A to the voltage disconnect phase A (red wire)
•Connect meter terminal B to the voltage disconnect phase B (black wire)
•Connect meter terminal C to the voltage disconnect phase C (blue wire)
•Connect meter neutral terminal to neutral bar in the voltage disconnect panel (white wire)
•Connect earth wire to earth post using lug provided
•Install power supply shorting jumpers (see Figure 6)
Figure 6: PowerLogic EM4000 meter 208Y/120V three-phase wye service connection
2 | 3 | 4 | 5 |
1
8
7
9 | 6 |
Legend:
1BX cable
2 Earth
3 Phase C (blue)
4 Phase B (black)
5 Shorting jumper
6 Sense voltage terminal block (J3)
7 Neutral (white)
8 Phase A (red)
9