Schneider Electric EM4000 manual Schneider Electric All Rights Reserved

Models: EM4000

1 44
Download 44 pages 33.45 Kb
Page 22
Image 22

PowerLogicTM Series EM4000

930-134-01-A.00

Installation Guide

11/2013

 

 

For a 208Y/120V three-phase wye panel with the 120V variant of the meter:

Connect meter terminal A to the voltage disconnect phase A (red wire)

Connect meter terminal B to the voltage disconnect phase B (black wire)

Connect meter terminal C to the voltage disconnect phase C (blue wire)

Connect meter neutral terminal to neutral bar in the voltage disconnect panel (white wire)

Connect earth wire to earth post using lug provided

Install power supply shorting jumpers (see Figure 6)

Figure 6: PowerLogic EM4000 meter 208Y/120V three-phase wye service connection

2

3

4

5

1

8

7

9

6

Legend:

1BX cable

2 Earth

3 Phase C (blue)

4 Phase B (black)

5 Shorting jumper

6 Sense voltage terminal block (J3)

7 Neutral (white)

8 Phase A (red)

9 0.75-inch (1.9-cm) strain relief

14

©2013 Schneider Electric All Rights Reserved

Page 22
Image 22
Schneider Electric EM4000 manual Schneider Electric All Rights Reserved