PowerLogicTM Series EM4000

930-134-01-A.00

Installation Guide

11/2013

 

 

Table 1: PowerLogic EM4000 series meter specifications

Specification

PowerLogic EM4033 meter

PowerLogic EM4080 meter

 

 

 

Dimensions

Height: 13.125 in. (33.5 cm)

Height: 13.125 in. (33.5 cm)

 

Width: 12 in. (30.5 cm)

Width: 12 in. (30.5 cm)

 

Depth: 2.125 in. (5.5 cm)

Depth: 2.125 in. (5.5 cm)

 

 

 

Weight

8.77 lb (3.98 kg)

8.77 lb (3.98 kg)

 

 

 

Sense voltage

100V to 300V 50/60Hz

100V to 300V 50/60Hz

 

2W+N+Protective Earth Wye

2W+N+Protective Earth Wye

 

3W+N+Protective Earth Wye

3W+N+Protective Earth Wye

 

3W+Protective Earth Delta

3W+Protective Earth Delta

 

 

 

Control voltage and current

North America:

North America:

 

• 120V 125 mA 60 Hz

• 120V 125 mA 60 Hz

 

• 277V 54 mA 60 Hz

• 277V 54 mA 60 Hz

 

 

 

Current transformers

0.333 V secondary CT

80 mA secondary CT

Measurement Category III

Note: All CTs used with the product

200 A primary CT

 

must be UL recognized/listed.

Meter burden: 4.04 ohms

 

 

 

 

CT burden: 20 ohms

 

 

Part number: METSECT80200

 

 

Note: All CTs used with the product

 

 

must be UL recognized/listed.

 

 

 

Measurement accuracy

ANSI C12.20 Class 0.5

ANSI C12.20 Class 0.5

(Accuracy compliant when used

IEC 62053-22 Class 0.5S

IEC 62053-22 Class 0.5S

with 0.3% CTs)

 

Measurement Canada Approved

 

 

EG07 compliant

 

 

 

Pulse inputs 1 and 2

Dry form A and solid-state form A

Dry form A and solid-state form A

 

compatible

compatible

 

Internal 3.3 V pull-up

Internal 3.3 V pull-up

 

Maximum frequency 10 Hz

Maximum frequency 10 Hz

 

Minimum pulse width 20 ms

Minimum pulse width 20 ms

 

 

 

Non-volatile memory storage

120 days in 15-minute intervals

120 days in 15-minute intervals

 

 

 

Onboard Ethernet port

10/100 Mb/s

10/100 Mb/s

 

 

 

Onboard Modbus RTU serial port

RS422 or RS485 19200/9600 Baud

RS422 or RS485 19200/9600 Baud

 

 

 

Fuse rating (F1)

North America:120V: T125 mA, 250V

North America:120V: T125 mA, 250V

 

 

 

Environmental

 

 

 

 

 

Operating temperature

-40 to 70oC

-40 to 70oC

Operating humidity

5% to 90% non-condensing

5% to 90% non-condensing

 

 

 

Usage environment

Indoor or enclosed outdoor environment

Indoor or enclosed outdoor environment

 

 

 

Maximum altitude

9843 ft (3000 m)

9843 ft (3000 m)

 

 

 

Pollution degree

2

2

 

 

 

Installation Category

II

II

 

 

 

Measurement Category

III

III

 

 

 