Installation Guide

11/2013

 

 

Installation

This section contains the following installation topics:

“Pre-Installation” on page 6

“Installation Procedures” on page 7

“Connecting Pulse Inputs” on page 26

Pre-Installation

The pre-installation checklist and site planning must be performed before installing the equipment at the site.

Receiving

The equipment required for each PowerLogic EM4000 meter installation includes:

high-density meter (PowerLogic EM4033 or PowerLogic EM4080)

For the PowerLogic EM4033 and PowerLogic EM4080, one 12-ft (4-m) AMP cable with one 50-pin connector supplied with each unit

CD and meter configuration software, this installation manual and an installation record form

When you receive your order, verify that the items listed above are included with the shipment, and visually inspect them for damage. If any parts are missing or damaged, contact your Schneider Electric representative.

Pre-Installation Checklist

The installer must provide the following information, tools, and equipment before proceeding with the installation:

certified current transformers for metering (not supplied)

an appropriate 15-Amp maximum circuit breaker or a fused disconnect switch for the type of panel

current/voltage meter to test the phasing of panels

RJ45 Ethernet patch cable

4-wire 14 AWG (1.63 mm2) cable for three-phase wye connected circuits, or 3-wire 14 AWG (1.63 mm2) cable for a single-phase wye connected circuits

small flat-head screwdriver

#2 Phillips screwdriver

crimping tool

18 AWG butt splice connector

wire strippers

four 1-inch (25 mm) #8 mounting screws suitable for selected mounting surface

Site Planning

1.Determine the number of PowerLogic EM4000 series meters to be installed and ensure adequate space. For clearances, see Figure 3 on page 8.

2.Determine the number of Ethernet drops required, and ensure they are installed before installing the PowerLogic EM4033 and EM4080 meters.