Schneider Electric EM4000 manual Introduction, System Description

Models: EM4000

1 44
Download 44 pages 33.45 Kb
Page 9
Image 9

930-134-01-A.00

PowerLogicTM Series EM4000

11/2013

Installation Guide

 

 

Introduction

This document describes the PowerLogic EM4033 and EM4080 meters, including procedures to install and start up the unit, and complete the initial configuration:

“System Description” on page 1

“Pre-Installation” on page 6

“Installation Procedures” on page 7

“Connecting Pulse Inputs” on page 26

“Fuse Replacement” on page 30

This documentation is intended for those responsible for installing and configuring the PowerLogic EM4033 and EM4080 meters. Installers must be qualified electricians with knowledge of local and national code requirements. See “Safety Precautions” on page 5.

System Description

The PowerLogic EM4033 and EM4080 meters support:

single-phase, 2-wire

single-phase, 3-wire (network)

three-phase wye and Delta services

Depending on how the meters are installed and configured, they can meter 8, 12, or 24 individual meter points. The PowerLogic EM4033 and EM4080 meters are designed for residential, commercial, and industrial use and display the power and consumption readings for each measurement point.

PowerLogic EM4000 series System Specifications

The PowerLogic EM4000 series system architecture includes:

single-phase, 2-wire; single-phase, 3-wire (network); three-phase, 4-wire (wye); and three-phase, 3-wire (delta) compatibility

2 control voltage variants: 120V 60Hz and 277V 60Hz

120/208V, 120/240V and 277/480V configurations, and 347/600V with external potential transformers

up to 8, 12, or 24 individual meter points

local Ethernet configuration interface via PC and web browser

Ethernet port for remote reporting

Modbus RTU serial port, for remote reporting

serial port for remote display

2 pulse inputs to connect metering devices

Table 1 lists the system specifications of the PowerLogic EM4033 and EM4080 meters.

©2013 Schneider Electric All Rights Reserved

1

Page 9
Image 9
Schneider Electric manual Introduction, System Description, PowerLogic EM4000 series System Specifications