Specifications
A–2 975-0239-01-01
Electrical Specifications

Table A-1

XW Power System Electrical Specifications

Model XW6048-120/240-60 XW4548-120/240-60 XW4024-120/240-60
Continuous Output Power 6,000 W 4,500 W 4,000 W
Surge Rating (10 seconds) 12,000 W 9,000 W 8,000 W
Surge Current L-n: 105 Arms (7 sec)
L-L: 52.5 Arms (7 sec)
L-n: 75 Arms (20 sec)
L-L: 40 Arms (20 sec)
L-n: 70 Arms (7 sec)
L-L: 35 Arms (7 sec)
Waveform True Sine Wave
Idle Consumption—invert mode, no load 28 W 26 W 24 W
Idle Consumption—search mode < 8 W
AC Output Voltage L-n: 120 Vac ±3%
L-L: 240 Vac ±3%
AC Input voltage range (Bypass/Charge
Mode)
L-n: 80–150 Vac (120 V nominal)
L-L: 160–270 Vac (240 V nominal)
AC Input Current (maximum 75%
imbalance between L1-n, L2-n)
L-n: 41.2 A
L-L: 27.5 A
L-n: 30.9 A
L-L: 20.6 A
L-n: 27.5 A
L-L: 18.3 A
AC Input Breaker 60 A double-pole
AC Input Frequency Range (Bypass/
Charge Mode)
55–65 Hz (default)
44–70 Hz (allowable)
AC1 voltage range—Sell Modea
(automatically adjusts when entering Sell
Mode)
a.This unit or system is provided with fixed trip limits and shall not be aggregated above 30 kW on a single Point of
Common Connection
L-n: 108–130 ±1.5 Vac
L-L: 214–260 ±3.0 Vac
AC1 Frequency range—Sell Modea
(automatically adjusts when entering Sell
Mode)
59.4–60.4 ±0.05 Hz
AC Output Current (maximum 75%
imbalance between L1-n, L2-n)
L-n: 37.5 A
L-L: 25.0 A
L-n: 28.1 A
L-L: 18.8 A
L-n: 25.0 A
L-L: 16.7 A
AC Output Breaker 60 A double-pole
AC Output Frequency 60.0 ±0.1 Hz
Total Harmonic Distortion < 5%
Automatic Transfer Relay 60 A
Auxiliary Relay Output 0–12 Vdc, maximum 250 mA DC
CEC Weighted Efficiency 93.5% 93% 91%
CEC Power Rating 6,000 W 4,500 W 4,000 W
DC Input Voltage (Nominal) 50.4 Vdc 50.4 Vdc 25.2 Vdc
DC Input Voltage Range 44–64 Vdc 44–64 Vdc 22–32 Vdc
DC Current at Rated Power 127 A 95 A 171 A
Continuous Charge Rate at L-L voltage 100 A 85 A 150 A
Power Factor Corrected Charging PF (0.98)