Step 4: Wiring the Inverter
Torque Values for the XW Power Distribution Panel
Table | Torque Values for AC Disconnects and AC Breakers | |||
Wire Size |
| Torque Value | ||
| ||||
|
|
|
|
|
AWG |
| |||
|
|
|
|
|
| 45 | 5 |
| |
8 |
| 45 | 5 |
|
| 45 | 5 |
| |
|
|
|
|
|
Table
Wire Size | Torque Value | ||
|
|
| |
AWG |
| ||
|
|
| |
14 - 10 | 35 | 4.0 | |
8 |
| 40 | 4.5 |
6 | - 4 | 45 | 5.1 |
3 | - 2/0 | 50 | 5.6 |
|
|
|
|
Table
Wire Size | Torque Value | ||
|
|
| |
AWG | |||
|
|
| |
14 - 10 | 35 | 4.0 | |
8 |
| 40 | 4.5 |
6 | - 4 | 45 | 5.1 |
3 | - 2/0 | 50 | 5.6 |
|
|
|
|
Table
Positive Bus in the XW Power Distribution Panel
| Torque Value | |
|
|
|
| ||
|
|
|
15 |
| 20.4 |
|
|
|
Inverter Grounding
Important: The grounding requirements vary by country and by application. All installations must comply with national and local codes. Consult local and national codes for specific grounding and bonding requirements for the desired installation.
Backfeed Protection Requirements
Important: Installers must make allowance for the amount of power that can be fed into a distribution panel and the means and location for