Inverter/Charger Installation

Wiring the Inverter to the XW Power Distribution Panel

Important: If a XW Conduit Box is installed, communication and Battery Temperature Sensor cables must run through the raceway at the rear of the XW Conduit Box. Before making AC and DC connections, route all communication and Battery Temperature Sensor cables through the raceways. The raceways becomes more difficult to access after all AC and DC wiring is completed.

Grounding the DC System

The inverter’s chassis ground bar (see Figure 2-7) is used to connect the chassis of the inverter to the DC grounding system. The terminal accepts wires from #14 AWG to #2 AWG.

A

See Table 2-5 on page 2–10 for torque values for the AC Chassis Ground.

B B

See Table 2-6 on page 2–10 for torque values for the Ground bar in the XW Power Distribution Panel.

A

Actual ground requirements may vary.

Figure 2-7DC Grounding Using a Power Distribution Panel

2–12

975-0239-01-01

Page 36
Image 36
Xantrex Technology XW6048-120/240-60 manual Wiring the Inverter to the XW Power Distribution Panel, Grounding the DC System