Inverter/Charger Installation

Making AC Connections

This section describes how to make AC connections between the XW Inverter/Charger and the XW Power Distribution Panel (using the pre-installed AC wiring in the XW Power Distribution Panel) and between the XW Power Distribution Panel and the AC distribution panel, or sub-panel (using wiring provided by the installer). See Appendix C, “Alternate System Configurations” if the installation will not be including an XW Power Distribution Panel.

CAUTION: Damage to the Inverter

The inverter’s AC output must never be wired to the utility or generator output. This will cause severe damage to the inverter which is not covered under warranty.

Do not use a GFCI equipped AC source to power either the grid or generator inputs. The AC input filters on the XW may cause nuisance tripping of ground fault protected outputs.

AC Connections and Communication Ports

AC Connections

The AC terminal block includes three terminals each (L1, L2 and Neutral) for AC Grid

 

input, AC Generator input, and AC Load connections. The neutrals are connected to each

 

other, requiring only one neutral connection when installed with an XW Power

 

Distribution Panel. Without the XW Power Distribution Panel, additional neutral

 

connections may be required at the input sources.

Communication

Four communications ports and one AUX Port are located on the bottom of the inverter

Ports

and support the following features.

 

• The two AC sync ports are used for connecting multiple inverters in parallel.

 

• The two Xanbus ports are used for network connections between inverters, charge

 

controllers, and accessories.

 

• The AUX port provides 12 Vdc/250 mA output to control a relay, fan, indicator light

 

or other device. The auxiliary output can be configured (using a XW System Control

 

Panel) to trigger in response to low- or high-battery voltage or high- or low-battery

 

temperature. The auxiliary output can also be triggered manually using a XW System

 

Control Panel.

AC access panel

AC terminal block

 

AC OUT

AC IN

AC IN

 

 

 

 

 

 

L1

N

L2

L1 N L2 L1 N L2

 

AC

 

GRID

GEN

LOAD

(AC1)

(AC2)

xantrex

Hybrid Inverter /Charger

Dual-knockouts

Communications Ports

 

 

 

 

 

(¾"–1")

AC sync ports

 

 

 

Xanbus ports

 

 

 

(RJ45) (×2)

 

 

(RJ45) (×2)

 

 

 

 

 

 

AUX port

Bottom View

Figure 2-12XW Inverter/Charger AC Connections and Communications Ports

2–16

975-0239-01-01

Page 40
Image 40
Xantrex Technology XW4024-120/240-60, XW6048-120/240-60 manual Making AC Connections, AC Connections and Communication Ports