Inverter/Charger Installation
Making AC Connections
This section describes how to make AC connections between the XW Inverter/Charger and the XW Power Distribution Panel (using the
CAUTION: Damage to the Inverter
The inverter’s AC output must never be wired to the utility or generator output. This will cause severe damage to the inverter which is not covered under warranty.
Do not use a GFCI equipped AC source to power either the grid or generator inputs. The AC input filters on the XW may cause nuisance tripping of ground fault protected outputs.
AC Connections and Communication Ports
AC Connections | The AC terminal block includes three terminals each (L1, L2 and Neutral) for AC Grid |
| input, AC Generator input, and AC Load connections. The neutrals are connected to each |
| other, requiring only one neutral connection when installed with an XW Power |
| Distribution Panel. Without the XW Power Distribution Panel, additional neutral |
| connections may be required at the input sources. |
Communication | Four communications ports and one AUX Port are located on the bottom of the inverter |
Ports | and support the following features. |
| • The two AC sync ports are used for connecting multiple inverters in parallel. |
| • The two Xanbus ports are used for network connections between inverters, charge |
| controllers, and accessories. |
| • The AUX port provides 12 Vdc/250 mA output to control a relay, fan, indicator light |
| or other device. The auxiliary output can be configured (using a XW System Control |
| Panel) to trigger in response to low- or |
| temperature. The auxiliary output can also be triggered manually using a XW System |
| Control Panel. |
AC access panel
AC terminal block
| AC OUT | AC IN | AC IN |
| |||
| |||
|
|
|
|
L1 | N | L2 | L1 N L2 L1 N L2 | |
| AC |
| GRID | GEN |
LOAD | (AC1) | (AC2) |
xantrex
Hybrid Inverter /Charger
Communications Ports | |||||
|
|
|
|
| |
AC sync ports |
|
|
| Xanbus ports | |
|
| ||||
| (RJ45) (×2) |
|
| (RJ45) (×2) | |
|
|
|
|
|
|
AUX port