Inverter/Charger Installation

Pre-Installation

Before installing the XW Inverter/Charger, read all instructions and cautionary markings located in this manual.

Important: Be sure to obtain the appropriate permits, if necessary, prior to starting this installation. Installations must meet all local codes and standards. Installations of this equipment should only be performed by skilled personnel such as qualified electricians and Certified Renewable Energy (RE) System installers.

 

WARNING: Personal Injury

 

The XW Inverter/Charger weighs approximately 120 pounds (54 kg). To prevent personal injury,

 

always use proper lifting techniques and have someone available to assist with lifting during

 

installation.

Location

 

 

 

The XW Inverter/Charger is certified for indoor (heated or unheated) installations only.

Close to battery

Locate the inverter as close to the batteries as possible in order to keep the battery cable

bank

length short. The maximum recommended battery cable length is 10 feet (3 m).

 

WARNING: Explosion and Corrosion Hazard

 

Do not locate the inverter directly above the batteries or in the same compartment as vented

 

batteries.

 

 

 

Locate any electronic equipment susceptible to radio frequency and electromagnetic

 

interference as far away from the inverter as possible.

Fire safety

Do not locate the inverter near readily flammable materials such as cloth, paper, straw, or

 

plastic sheeting. Flammable materials should be kept a minimum distance of 24 inches

 

(60 cm) from the top surface and 12 inches (30 cm) from either side surface and the front

 

of the XW Inverter/Charger.

Knockout Preparation

Remove your choice of knockouts from the chassis to facilitate conduit installation for wire runs. Ensure no debris from this procedure remains inside the inverter enclosure.

Important: Do not drill, cut, or punch holes into the XW power distribution

Panel. Use only the knockouts provided for conduit entry.

2–2

975-0239-01-01

Page 26
Image 26
Xantrex Technology XW4548-120/240-60, XW6048-120/240-60, XW4024-120/240-60 Pre-Installation, Location, Knockout Preparation