Schneider Electric EM4000 manual From Panel

Models: EM4000

1 44
Download 44 pages 33.45 Kb
Page 23
Image 23

930-134-01-A.00

PowerLogicTM Series EM4000

11/2013

Installation Guide

 

 

For a 480Y/277V three-phase wye panel with the 277V variant of the meter:

Connect meter terminal A to the voltage disconnect phase A (red wire)

Connect meter terminal B to the voltage disconnect phase B (black wire)

Connect meter terminal C to the voltage disconnect phase C (blue wire)

Connect meter neutral terminal to neutral bar in the voltage disconnect panel (white wire)

Connect earth wire to earth post using lug provided

From the auxiliary power transformer, connect 120V auxiliary power to AUXA and AUXN on the meter (see Figure 7)

Figure 7: PowerLogic EM4000 meter 480Y/277V three-phase wye service connection

 

 

AUX_N

 

 

AUX_A

FROM PANEL

 

C

 

 

B

 

 

A

A

N

N

©2013 Schneider Electric All Rights Reserved

15

Page 23
Image 23
Schneider Electric EM4000 manual From Panel