Schneider Electric EM4000 manual 930-134-01-A.00

Models: EM4000

1 44
Download 44 pages 33.45 Kb
Page 19
Image 19

930-134-01-A.00

PowerLogicTM Series EM4000

11/2013

Installation Guide

 

 

Installing the Sense Voltage and Control Voltage Cables in Wye and

Delta Services

The sense voltage (A, B, C, N) provides phase voltages for metering. The configuration depends on the type of service being metered:

• see “For a single-phase panel with the 120V variant of the meter:” on page 13

• see “For a 208Y/120V three-phase wye panel with the 120V variant of the meter:” on page 14

• see “For a 480Y/277V three-phase wye panel with the 277V variant of the meter:” on page 15

• see “For a 600Y/347V or higher three-phase wye panel with potential transformers with the 120V variant of the meter:” on page 16

• see “For a three-phase Delta panel with the 120V variant of the meter:” on page 17

The PowerLogic EM4033 and EM4080 meters are shipped from the factory with a control voltage jumper that can be used to connect the control voltage input and the sense voltage inputs to provide control voltage to the unit. The following procedures explain how to connect the sense voltage inputs for each of the service types.

For a single-phase panel, use a 3-wire (red, black, white), 14 AWG (1.63 mm2),

90oC (194oF) cable. For a three-phase panel, use a 4-wire (red, black, blue, white), 14 AWG (1.63 mm2), 90oC (194oF) cable. For a Delta service, use a 3-wire (red, black, blue), 14 AWG (1.63 mm2), 90oC (194oF) cable. Metallic, flexible armored cable (BX cable) is recommended for commercial installations as shown in Figure 5 on page 13.

The PowerLogic meters must be connected to the sense voltage and control voltage through a properly rated disconnect that disconnects all line and neutral wires, so it can be powered down. The disconnect must be located within easy reach of the meter operator, and must be labeled as such. Opening the disconnect or breaker is the disconnect device. For multiple PowerLogic meter installations, the same disconnect can be used to power all meters, and must be labeled for all meters it supplies power to. The disconnect device must meet IEC 60947-1, IEC 60947-3 and/or comply with the local electrical code.

©2013 Schneider Electric All Rights Reserved

11

Page 19
Image 19
Schneider Electric EM4000 manual 930-134-01-A.00