Display Navigation

The PowerLogic EM4000 meter has three buttons to control the information presented on the LCD. The display has a normal and a diagnostics mode. The PowerLogic EM4000 meter starts in normal mode, and enters diagnostics mode when the Display button is pressed and held for 5 seconds. To adjust the contrast, hold down the Display button, and use the right and left arrow buttons to increase and decrease the contrast respectively.

Normal Mode

In Normal mode, the Display button scrolls through the information for each meter. The left and right arrow buttons select the previous or next meter points respectively. The following information is available:

• Real Energy Delivered kWh D

• Real Energy Received kWh R

• Real Power Watts

• Reactive Energy Delivered kVarhD

• Reactive Energy Received kVarhR

• Reactive Power Var

• Peak Demand Peak W (Watts)

In Normal mode, the right and left arrow buttons scroll the display from meter points 1 to 8, 1 to 12, or 1 to 24, depending on your configuration.

Diagnostics Mode

Diagnostics mode is accessed by pressing and holding the Display button for 5 seconds. In Diagnostics mode, pressing the Display button will scroll through the following additional information:

Send data command

CT Primary value and Real Power Watts per phase

Current (Amps) per phase

Power factor (pf) per phase

Phase angle (degrees) per phase

Voltage per phase

Local IP address

Reset factory default IP address command

Verify

Badge #

Date and time (UTC)

In Diagnostics mode, the right and left arrow buttons scroll the display from meter 1 to 8, 1 to 12, or 1 to 24, depending on your configuration. When the local IP address is shown on the LCD, use the right and left arrow buttons to scroll through the following information:

Remote host server IP address

Time server IP address

Default IP address

Default NetMask

©2013 Schneider Electric All Rights Reserved