PowerLogicTM Series EM4000

930-134-01-A.00

Installation Guide

11/2013

 

 

For a 600Y/347V or higher three-phase wye panel with potential transformers with the 120V variant of the meter:

Connect meter terminal A to the voltage disconnect phase A (red wire)

Connect meter terminal B to the voltage disconnect phase B (black wire)

Connect meter terminal C to the voltage disconnect phase C (blue wire)

Connect meter neutral terminal to neutral bar in the voltage disconnect panel (white wire)

Connect earth wire to earth post using lug provided

Install power supply shorting jumpers (see Figure 8)

NOTE: For the wiring of the potential transformers, see Figure 4.

Figure 8: PowerLogic EM4000 meter 600Y/347V or higher three-phase wye service with potential transformers connection

2

3

4

5

1

8

7

9

6

Legend:

1BX cable

2 Earth

3 Phase C (blue)

4 Phase B (black)

5 Shorting jumper

6 Sense voltage terminal block (J3)

7 Neutral (white)

8 Phase A (red)

9 0.75-inch (1.9-cm) strain relief

16

©2013 Schneider Electric All Rights Reserved