Schneider Electric INTERBUS Basic Network Interface Module manual NIM Activity, LEDs

Models: 890USE19600 Version 1.0 INTERBUS Basic Network Interface Module

1 71
Download 71 pages 16.46 Kb
Page 23
Image 23
NIM Activity

The STB NIB 1010 Basic NIM Module

INTERBUS Data The following table describes the indicated condition(s) and the colors and blink Exchange LEDs patterns that the RC, BA and RD LEDs use to show normal operations and error

conditions for the NIM on an INTERBUS fieldbus.

Label

Pattern

Meaning

 

 

 

BA (green)

on

The module is transmitting data messages on the network.

 

 

 

 

off

The module is not transmitting data messages on the network.

 

 

 

RC (green)

on

The island’s incoming bus is correctly connected, and the bus master device is not

 

 

sending a bus reset signal.

 

 

 

 

off

The island’s incoming bus is not correctly connected, or the bus master device is sending

 

 

a bus reset signal.

 

 

 

RD (yellow)

on

The island’s outgoing bus is disabled.

 

 

 

 

off

The island’s outgoing bus is enabled.

 

 

 

NIM Activity

The table that follows describes the island bus condition(s) communicated by the

LEDs

LEDs, and the colors and blink patterns used to indicate each condition.

 

 

 

 

RUN (green)

 

ERR (red)

Meaning

 

 

 

 

blink 2

 

blink 2

The island is powering up (self test in progress).

 

 

 

 

off

 

off

The island is initializing—it is not started.

 

 

 

 

blink 1

 

off

The island has been put in the pre-operational state by the RST button—it is

 

 

 

not started.

 

 

 

 

blinking (steady)

 

off

The NIM is auto-configuring the island bus—the bus is not started.

 

 

 

 

blink 3

 

off

Initialization is complete, the island bus is configured, the configuration

 

 

 

matches, and the bus is not started.

 

 

 

 

off

 

blink 6

The NIM detects no STB I/O modules on the island bus.

 

 

 

 

off

 

blink 2

Assignment error—the NIM has detected a module assignment error; the

 

 

 

island bus is not started.

 

 

 

 

 

 

blink 5

Internal triggering protocol error.

 

 

 

 

off

 

blinking

Fatal error. Because of the severity of the error, no further communications

 

 

(steady)

with the island bus are possible and the NIM stops the island. The following

 

 

 

are fatal errors:

 

 

 

significant internal error

 

 

 

module-ID error

 

 

 

auto-addressing failure

 

 

 

process image error

 

 

 

auto-configuration error

 

 

 

￿island bus management error

 

 

 

receive/transmit queue software overrun error

 

 

 

 

on

 

off

The island bus is operational.

 

 

 

 

on

 

blink 3

At least one module does not match—the island bus is operational with a

 

 

 

configuration mismatch.

 

 

 

 

blink 4

 

off

The island bus is stopped—no further communications with the island are

 

 

 

possible.

 

 

 

 

off

 

on

Fatal error—internal failure.

 

 

 

 

890USE19600 April 2004

23

Page 23
Image 23
Schneider Electric INTERBUS Basic Network Interface Module, 890USE19600 Version 1.0 manual NIM Activity, LEDs