Data Exchange

Fieldbus Communications Support

Data Exchange

Introduction Process image data is exchanged between the STB NIB 1010 NIM and an INTERBUS fieldbus master in a bit-packed format.

Note: In this discussion, data and words described as input and output are defined relative to the master. For example, the master receives input data and transmits output data.

Data and Status

Data exchange between the island and the INTERBUS master involves three types

Objects

 

of objects:

 

 

 

 

 

 

data objects—operating values the INTERBUS master either reads from the input

 

 

 

modules or writes to the output modules

 

 

 

 

 

status objects—module health records sent by I/O modules and read by the

 

 

￿

INTERBUS master

 

 

 

 

 

 

echo output data objects—sent by digital object modules to the INTERBUS

 

 

 

master; these objects are usually a copy of the data objects, but they can contain

 

 

 

useful information when a digital output point is configured to handle the result of

 

 

 

a reflex action

 

 

 

 

 

Standard Advantys STB I/O modules support all three of the above objects. Basic

 

 

Advantys STB I/O modules support only data objects, not status or echo objects.

 

 

The following table shows the relationship between different object types and

 

 

different module types. It also shows the size of the different objects:

 

 

 

 

 

 

 

 

Module Type

 

 

 

Objects in the Input Data Image

Objects in the Output Data Image

 

 

 

 

 

 

 

 

 

 

 

 

Objects

Size

Objects

Size

 

 

 

 

 

 

 

 

digital input

 

 

 

data

1 byte or less

does not apply

 

 

 

 

 

 

 

 

 

 

 

 

 

status1

1 byte or less

does not apply

 

digital output

 

 

 

echo output data

1 byte or less

data

1 byte or less

 

 

 

 

 

 

 

 

 

 

 

 

status1

1 byte or less

does not apply

 

analog input

channel 1

 

data

2 bytes

does not apply

 

 

 

 

 

 

 

 

 

 

 

 

 

status2

1 byte

does not apply

 

 

channel 2

 

data

2 bytes

does not apply

 

 

 

 

 

 

 

 

 

 

 

 

 

status2

1 byte

does not apply

 

analog output

channel 1

 

status2

1 byte

data

2 bytes

 

channel 2

 

status2

1 byte

data

2 bytes

1 Echo and status information is not available for every module. For example, basic I/O modules do not report this information. Refer to The Advantys STB Hardware Components Reference Guide (890 USE 172 00) for details.

2 Status information is not available for every analog module. For example, basic analog modules do not report status. Refer to The Advantys STB Hardware Components Reference Guide (890 USE 172 00) for details.