Schneider Electric INTERBUS Basic Network Interface Module manual INTERBUS Data Length

Models: 890USE19600 Version 1.0 INTERBUS Basic Network Interface Module

1 71
Download 71 pages 16.46 Kb
Page 37
Image 37
Data Length

 

 

 

Fieldbus Communications Support

 

 

 

 

Data Length

The following table shows the relationship between the actual data length of the

 

island and the length of the code on INTERBUS. The actual data length (anywhere

 

from 0 to 16 words) represents the greater of the input or output data length.

 

 

 

Actual Length of Island Data

INTERBUS Data Length

Data Length Code (Hex)

 

 

 

 

up to 1 word*

 

1 word

1

 

 

 

 

2 words

 

2 words

2

 

 

 

 

3 words

 

3 words

3

 

 

 

 

4 words

 

4 words

4

 

 

 

 

5 words

 

5 words

5

 

 

 

 

6 words

 

6 words

E

 

 

 

 

7 words

 

7 words

F

 

 

 

 

8 words

 

8 words

6

 

 

 

 

9 words

 

9 words

7

 

 

 

 

10 words

 

10 words

15

 

 

 

 

11 to 12 words

 

12 words

16

 

 

 

 

13 to 14 words

 

14 words

17

 

 

 

 

15 to 16 words

 

16 words

12

 

 

 

 

17 to 24 words**

 

24 words

13

 

 

 

 

25 to 26 words**

 

26 words

11

 

 

 

* The status word is included in the data length, so the minimum allowable data length for an Advantys island is 2

words (data word + status word).

 

 

** The STB NIB 1010 INTERBUS NIM supports only up to 16 words in each direction (input/output).

 

 

 

 

 

 

 

 

890USE19600 April 2004

37

Page 37
Image 37
Schneider Electric INTERBUS Basic Network Interface Module manual Actual Length of Island Data, INTERBUS Data Length