CME1356R and CME1656R

Remote Condenser Location

Use the following for planning the placement of the condenser relative to the ice machine

Location Limits - condenser location must not exceed ANY of the following limits:

Maximum rise from the ice machine to the condenser is 35 physical feet

Maximum drop from the ice machine to the condenser is 15 physical feet

Physical line set maximum length is 100 feet.

Calculated line set length maximum is 150.

Calculation Formula:

Drop = dd x 6.6 (dd = distance in feet)

Rise = rd x 1.7 (rd = distance in feet)

Horizontal Run = hd x 1 (hd = distance in feet)

Calculation: Drop(s) + Rise(s) + Horizontal Run = dd+rd+hd = Calculated Line Length

Do NOT:

Route a line set that rises, then falls, then rises.

Route a line set that falls, then rises, then falls.

Calculation Example 1:

The condenser is to be located 5 feet below the ice machine and then 20 feet away horizontally.

5 feet x 6.6 = 33. 33 + 20 = 53. This location would be acceptable

Calculation Example 2:

The condenser is to be located 35 feet above and then 100 feet away horizontally.

35 x 1.7 = 59.5. 59.5 +100 = 159.5. 159.5 is greater than the 150 maximum and is NOT acceptable.

Configurations that do NOT meet these requirements must receive prior written authorization from Scotsman.

Operating a machine with an unacceptable configuration will void the refrigeration system warranty.

 

 