CME1356R and CME1656R
Service Diagnosis
Problem or Symptom | Possible Cause  | Probable Correction  | 
  | 
  | 
  | 
  | Scale in water system.  | Clean water system.  | 
  | 
  | 
  | 
  | Water or Air Temperatures too  | Check temps. Unit cannot  | 
  | operate with water and air  | |
  | cold  | |
  | temps below stated limits.  | |
  | 
  | |
  | Low system charge  | Recover and weigh charge.  | 
  | Bypass solenoid does not open  | Check solenoid operation  | 
Poor Harvest  | Check valve leaks back  | Replace check valve  | 
  | ||
  | 
  | 
  | 
  | 
  | Check for power to the coil, if  | 
  | Hot gas valve does not open  | there is power, replace the hot  | 
  | 
  | gas valve  | 
  | 
  | 
  | 
  | Head pressure control valve  | Replace the head pressure  | 
  | does not maintain enough  | |
  | control valve  | |
  | pressure (in freeze)  | |
  | 
  | |
  | 
  | 
  | 
  | High discharge pressure, from a  | Clean the condenser, repair the  | 
  | dirty condenser or faulty fan  | |
  | fan motor  | |
  | motor  | |
  | 
  | |
  | Extreme hot location  | Relocate the cabinet  | 
  | Extremely hot condenser  | Move condenser or provide  | 
  | location  | shade  | 
  | 
  | 
  | 
  | Overcharge of refrigerant  | Recover, evacuate and weigh in  | 
  | the nameplate charge  | |
Low capacity  | 
  | |
  | 
  | |
  | At the end of the freeze cycle,  | |
  | 
  | |
  | 
  | there should be a definite  | 
  | Hot gas valve leaks thru, unit off  | difference in temperature  | 
  | on refrigeration error  | between the inlet and outlet of  | 
  | 
  | the Hot Gas Valve. If not,  | 
  | 
  | replace the hot gas valve  | 
  | Liquid and discharge lines are  | Separate and insulate them  | 
  | in contact with each other  | |
  | 
  | |
  | 
  | Low on refrigerant, locate leak,  | 
  | 
  | recover refrigerant, repair leak,  | 
  | 
  | replace drier, evacuate and  | 
  | 
  | weigh in the nameplate charge.  | 
  | 
  | 
  | 
  | 
  | TXV superheat too high, check  | 
  | 
  | charge, if charge is OK, replace  | 
Compressor cycles on and off  | Compressor overheats  | TXV | 
  | 
  | Mechanical fault with  | 
  | 
  | compressor, replace  | 
  | 
  | compressor  | 
  | 
  | Internal relief valve opened,  | 
  | 
  | check for cause of high  | 
  | 
  | discharge pressure  | 
  | 
  | 
  | 
  | 
  | 
  | 
May 2001
Page 34