And then adjust the speed by speed control knob and adjust to the No-load revolution.

 

 

 

No-load revolution

50 Hz

Operation

1575 min-1

(52.5 Hz)

60 Hz

Operation

1890 min-1

(63.0 Hz)

<Caution>

By adjusting the speed to the above revolutions, the frequency will be 50Hz or 60Hz.

Lock the Speed Control handle with locknut

<Caution>

Ensure that the speed control handle is surely locked with locknut, otherwise the frequency (engine revolution) may fluctuate.

Adjust to the required voltage by adjusting Voltage regulator.

Turn the circuit breaker to ON position to send power to the load side.

! Danger

:Electrical Shock ￿ Injuries

￿Before turning the circuit breaker to ON position to send power to the load side, always ensure that any circuit breaker and switch of loads are positioned to OFF.

In the case the generator and the load are away from each other, proceed with the above steps, communicating well with the other person by the load in order to prevent from accident.

9.2During Operation

9.2.1Post startup check

￿Make sure that all meters (gauges) and displays are working properly (refer to 5. Equipment)

￿Check for any unusual vibration or noise

￿Check for any unusual color from the exhaust. Under normal condition, the exhaust fume has no color or light bluish color.

<Caution>

If finding out abnormality, consult with the distributor or our engineering section in order to repair, without using the machine.