Limitations of C-Bus participants
8 Limitations of C-Bus participants
This chapter describes the quantitative limits of the FC700A station.
The selection of the station type depends on the requirements. The following vari- ants are available:
|
| Flash ROM | SRAM |
|
| |
Station type | Modules | (2x1024Kx8Bit) | EPROM set | RAM set | ||
Soldered | ||||||
|
| 'Program file' |
|
| ||
|
|
|
|
| ||
FC700A | B3Q700 | CIY00760 | 4x512Kx8Bit | – | – | |
FT700A | B3Q700 | CTY00760 | 4x512Kx8Bit | – | – | |
|
|
|
| CKQ007.60 | 2 x Z3S070 | |
FG700A | E3H020 | – | – | (2x512Kx8Bit) | ||
(2x512Kx8Bit) | ||||||
|
|
|
| (Assembly ex works) | ||
|
|
|
|
|
8.1Main CPU limits
8.1.1Maximum number of devices
1000 devices (with AMPK=1) per FC700A.
8.1.2Limits in the logical structure
The limits in the logical structure are given by the
Table 'Limits of the logical structure'
Maximum rating | Maximum rating | Maximum rating | Maximum rating |
AREAS per STATION | SECTIONS per AREA | ZONES per SECTION | ELEMENTS per ZONE |
... 4 | …255 | …255 | …99 |
|
|
| International 5: …255 |
8.1.3Maximum number of criteria in zones control 4 and 6
The maximum number of control zones with 16 criteria is limited by 200.
To optimize the performance of your system minimize the number of
A maximum of 40
8.1.4Maximum number of ZONE time channel
Max. 16 ZONES time channel are permitted per station.