Limitations of C-Bus participants

Limitations of C-Bus participants

8 Limitations of C-Bus participants

This chapter describes the quantitative limits of the FC700A station.

The selection of the station type depends on the requirements. The following vari- ants are available:

 

 

Flash ROM

SRAM

 

 

Station type

Modules

(2x1024Kx8Bit)

EPROM set

RAM set

Soldered

 

 

'Program file'

 

 

 

 

 

 

 

FC700A

B3Q700

CIY00760

4x512Kx8Bit

FT700A

B3Q700

CTY00760

4x512Kx8Bit

 

 

 

 

CKQ007.60

2 x Z3S070

FG700A

E3H020

(2x512Kx8Bit)

(2x512Kx8Bit)

 

 

 

 

(Assembly ex works)

 

 

 

 

 

8.1Main CPU limits

8.1.1Maximum number of devices

1000 devices (with AMPK=1) per FC700A.

8.1.2Limits in the logical structure

The limits in the logical structure are given by the node-type, by the highest possi- ble CSX number and the maximum amount of display-digits. These limits are given by the system and are independent of the memory capacity.

Table 'Limits of the logical structure'

Maximum rating

Maximum rating

Maximum rating

Maximum rating

AREAS per STATION

SECTIONS per AREA

ZONES per SECTION

ELEMENTS per ZONE

... 4

…255

…255

…99

 

 

 

International 5: …255

8.1.3Maximum number of criteria in zones control 4 and 6

The maximum number of control zones with 16 criteria is limited by 200.

To optimize the performance of your system minimize the number of CPU-overlapping controls as much as possible.

A maximum of 40 CPU-overlapping controls (zone control 6) are admissible per C-Bus.

8.1.4Maximum number of ZONE time channel

Max. 16 ZONES time channel are permitted per station.