Line modules
15.4Detection line "collective" SynoLINE600/-Ex
8 Stub lines
All detectors on a line have the same collective address (ZONE) Number of detectors per line max. 25 with KMK1
Line termination depending on application by means of Transzorb or EOL22 (Ex) Connectable types of detectors and connection see document 007831
1 |
| DLO1191 |
|
| DF1191/92 |
| |
DBZ1197A | DM1103 | HI62xC | OP620C |
Line termination: Transzorb 20V/EOL22
Line resistance: max.150Ω
2
SynoLINE600
E3M080
3 | DLR11 . . |
|
|
| ||
| DC1192 | DM1103 |
|
|
8 | ||||
|
|
| Line termination | |
|
|
|
| |
|
|
|
| EOL22 (Ex) |
OP620C | HI62xC | SB3 |
|
|
| 24VDC |
|
|
|
Some detectors have different loading factors, to evaluate how many special de- tectors can be connected to one collective line see chapter 16.2.