Siemens manual 12.6Power supply, Control unit FC700A, Loop C-Bus, EN54 requirements

Models: FC700A

1 70
Download 70 pages 19.31 Kb
Page 30
Image 30
Loop C-Bus

Control terminal B3Q700 (FC/FT)

12.5Connection lines between control unit and external operating units

Control terminal FT700A

Control terminal

Options

FT700A

 

B3R051 (Parallel indicator panel)

E3I040 (LON module)

 

Printer

 

2…11

 

leads

Loop C-Bus

max. 1000m per loop with 0,6mm G51 (incl. return line) max. 1400m per loop with 0,8mm G51 (incl. return line)

Control unit FC700A

When planning a system the following condition must be complied with:

At least one operating unit must comply with standard EN54, i.e. it must be equipped with emergency operation and emergency power supply.

EN54 requirements:

Communication as loop line -> design C-Bus as a loop line Operating units also with emergency operation -> 3 additional wires Second de-coupled 24V supply -> 3 additional wires or autonomous power supply

The number of wires in the connection cable depends on the application and the distances between the stations:

Application

C-Bus

24V supply

Emergency power

Emergency opera-

Number of wires

supply

tion circuit

 

 

 

 

24V supply from

11

control unit

(2 wires)

(3 wires)

(3 wires)

(3 wires)

EN54 complied with

 

 

 

 

 

 

24V supply from

 

 

 

 

 

control unit without

 

 

5

emergency operation

 

 

(2 wires)

(3 wires)

 

 

and emergency

 

 

 

 

 

 

 

 

power supply

 

 

 

 

 

Note:

Emergency operation circuit required including between CPUs or for a sepa- rately connected Gateway

Emergency operation circuit and emergency supply are not designed as a loop line

Emergency supply via separate cable or C-Bus feedback

12.6Power supply (24V)

Operating unit B3Q700 is designed for the voltage range 18...45VDC

The maximum current at 24V is 400mA

Max. Length of line (approximate):

For cables ø 0.8mm -> 180m

For cable cross-section 1mm2 -> 360m

 

The current consumption for the options (parallel indicator panel, LON-module)

 

must be taken into account separately

30

 

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

Page 30