Control terminal B3Q700 (FC/FT)
12.5Connection lines between control unit and external operating units
Control terminal FT700A | Control terminal |
Options | FT700A |
| |
B3R051 (Parallel indicator panel) | |
E3I040 (LON module) |
|
Printer |
|
2…11 |
|
leads | Loop |
max. 1000m per loop with ∅0,6mm G51 (incl. return line) max. 1400m per loop with ∅0,8mm G51 (incl. return line)
Control unit FC700A
When planning a system the following condition must be complied with:
At least one operating unit must comply with standard EN54, i.e. it must be equipped with emergency operation and emergency power supply.
EN54 requirements:
Communication as loop line
The number of wires in the connection cable depends on the application and the distances between the stations:
Application | 24V supply | Emergency power | Emergency opera- | Number of wires | ||
supply | tion circuit | |||||
|
|
|
| |||
24V supply from | ✔ | ✔ | ✔ | ✔ | 11 | |
control unit | ||||||
(2 wires) | (3 wires) | (3 wires) | (3 wires) | |||
EN54 complied with |
| |||||
|
|
|
|
| ||
24V supply from |
|
|
|
|
| |
control unit without | ✔ | ✔ |
|
| 5 | |
emergency operation |
|
| ||||
(2 wires) | (3 wires) |
|
| |||
and emergency |
|
|
| |||
|
|
|
|
| ||
power supply |
|
|
|
|
|
Note:
–Emergency operation circuit required including between CPUs or for a sepa- rately connected Gateway
–Emergency operation circuit and emergency supply are not designed as a loop line
–Emergency supply via separate cable or
12.6Power supply (24V)
Operating unit B3Q700 is designed for the voltage range 18...45VDC
The maximum current at 24V is 400mA
Max. Length of line (approximate):
–For cables ø 0.8mm
–For cable
| The current consumption for the options (parallel indicator panel, |
| must be taken into account separately |