Alarm concept
24.3Determine the alarm organization
–The FC700A fire detection system has up to 64 programmable organization lev- els (AREAS)
–A number of "Alarm variants" are possible (can be selected per ZONE)
–The time countdown memories "V1" and "V2" must be specified individually
–The time countdown memory "V2" can be defined per ZONE (if required)
–Various special local functions are provided
–The alarm organization is programmed individually (via maintenance PC)
24.4Organization of system operation
The place of operation of the fire detection system must be determined from an organizational point of view
If required a second operating facility must be provided
If operating units are particularly exposed, they must be fitted with a lockable Plexiglas door (H26T030 + Z3S200)
The type of event and the location are displayed on the operating unit in plain text
The locations (rooms etc.) are individually defined by means of the "User text" (via maintenance PC)
If required, an additional
The fire detection system may only be operated by instructed personnel (operat- ing access is therefore protected by password or key switch)
Details of control terminal FT700A see chapter 12