Power supply
22 Power supply
22.1Concept
The power supply for the FC700A fire detection system consists of:
Converter | (mains voltage |
Battery charging unit | (by means of E3C011) |
Batteries (lead) | (capacity as required) |
22.2Special functions
–Automatic battery load test
–Battery charging characteristic can be programmed according to make
22.3Application
–Determine required battery capacity individually
–Max. 27Ah per battery charging unit (> 27Ah = auxiliary power supply)
–Parallel operation of several battery charging units possible
–Battery lead without
22.4Power supply for the control unit
Battery charging module E3C011 required
Mains
FC
B2F020
40...220VA
29,6V
B3Q700
E3C011 Batteries AX12..
TF*
22.5Auxiliary power supply
FT |
* TF = Temperature sensor for battery temperature monitoring
MainsMains
Basic emergency power supply
Extension
Batteries | B2F020 |
|
| Batteries | ||
| B2F020 |
| ||||
TF* | AX12.. | TF* | AX12.. | |||
|
|
Battery charging
24V unit
E3C011
FC
E3C011
Monitoring via HW monitoring path
52
Siemens Building Technologies | |
Fire & Security Products | 03.2004 |