Siemens FC700A manual Power supply, 22.1Concept, 22.2Special functions, 22.3Application, Converter

Models: FC700A

1 70
Download 70 pages 19.31 Kb
Page 52
Image 52
Power supply

Power supply

22 Power supply

22.1Concept

The power supply for the FC700A fire detection system consists of:

Converter

(mains voltage -> system voltage 29,6V)

Battery charging unit

(by means of E3C011)

Batteries (lead)

(capacity as required)

22.2Special functions

Automatic battery load test

Battery charging characteristic can be programmed according to make

22.3Application

Determine required battery capacity individually -> see chapter 23

Max. 27Ah per battery charging unit (> 27Ah = auxiliary power supply)

Parallel operation of several battery charging units possible

Battery lead without EMI-protection (battery cannot be mounted separately)

22.4Power supply for the control unit

Battery charging module E3C011 required

Mains

FC

B2F020

40...220VA

29,6V

B3Q700

E3C011 Batteries AX12..

TF*

I-Bus

22.5Auxiliary power supply

FT

* TF = Temperature sensor for battery temperature monitoring

MainsMains

Basic emergency power supply

Extension

C-Bus

Batteries

B2F020

 

 

Batteries

 

B2F020

 

TF*

AX12..

TF*

AX12..

 

 

Battery charging

24V unit

E3C011

FC

E3C011

Monitoring via HW monitoring path

52

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004

Page 52
Image 52
Siemens FC700A 22.1Concept, 22.2Special functions, 22.3Application, 22.4Power supply for the control unit, Converter