Siemens FC700A manual 8.2Control terminal limits FC/FT, 8.1.5Maximum number of I-Bus-modules

Models: FC700A

1 70
Download 70 pages 19.31 Kb
Page 21
Image 21
8.1.5Maximum number of I-Bus-modules

Limitations of C-Bus participants

8.1.5Maximum number of I-Bus-modules

Table 'Maximum number of I-Bus-modules'

Station type

FC700A

I-Bus modules

... 16 1) ... 8 2) 3)

1)Limited by software

2)Value based on experience (depends on cabinet size and/or 5V current consumption)

3)Battery charging unit E3C011 counts as one I-Bus module

8.1.6Limits of 5V supply

All I-Bus modules are supplied with 24V and 5V. The available current for the 5V, supplied from main CPU is limited:

'Main CPU'

Available current

B3Q700 / E3C011

250mA

Table '5V-Current consumption of I-Bus modules'

I-Bus module

Current consumption

I-Bus module

Current consumption

from 'Main CPU'

from 'Main CPU'

 

 

E3M080

55mA

E3G060

10mA

E3M111

25mA

E3G070

10mA

E3L020

10mA

E3C011

12mA

E3L030

35mA

E3I020*

100mA

E3G050

8mA

E3I040

70mA

*Not an I-Bus module, but supplied via the 'Main CPU'

8.2Control terminal limits (FC/FT)

8.2.1Limitation of visible texts on a FC700A

The number of texts of other stations (i.e. AREAS) that can be displayed on one control terminal is limited by 14'000 texts.

To evaluate how many control panels FC700A can be displayed to one FC700A, the following calculation must be used:

Twice the number of visible sections (worst case 1000)

+The number of visible ZONES (worst case 1000)

+The number of visible ELEMENTS with element text (worst case 1000) = Number of texts per FC/FT (worst case 4000)

Example (worst case)

14'000 : 4000 (e.g.) = 3 fully configured FC can be displayed to one FC

8.2.2Limitation of visible texts on a FT700A

The number of texts of other stations (FC700A) that can be displayed on one con- trol terminal is limited by 14'000 texts.

To evaluate how many control panels FC700A can be displayed to one FT700A, the following calculation must be used:

Twice the number of visible sections (worst case 1000)

+The number of visible ZONES (worst case 1000)

+The number of visible ELEMENTS with element text (worst case 1000) = Number of texts per FC/FT (worst case 4000)

Example (worst case)

30'000 : 4000 (e.g.) = 7 fully configured FC can be displayed to one FT

 

21

 

 