Auxiliary power supply

Auxiliary power supply

11 Auxiliary power supply

11.1Configuration

Module chassis view 'Modules'

 

 

 

B2F020

 

 

 

Converter 115/230VAC

Cabinet front view

 

absolutely essential

-> 29.6VDC/6A

 

 

 

 

 

27

28

 

37

38

 

E3C011

Z3I470

B2F020

46

47

48

56

57

58

View A

23

Mains

terminals

31

AX1201

or

AX1210

51

AX1201

or

AX1210

H38G310

E3C011

Battery charging module

 

11 Auxiliary power supply A

Z3I470

Cable set, terminal strip with card holder

AX1201 / AX1210

Batteries

11.2Block diagram

* TF = Temperature sensor for battery temperature monitoring

Mains

Mains

FC700A

Basic emergency power supply

Batteries 11.1Configuration11.2Block diagram B2F020

TF* AX12..

Battery charging unit

E3C011

 

 

 

 

 

H38G310

 

 

Extension

 

 

 

 

 

 

 

 

 

 

 

B2F020

 

 

 

 

 

Batteries

 

 

TF*

 

AX12..

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E3C011

 

 

 

 

 

 

 

 

 

 

Cascading

Monitoring via HW monitoring path

Details see document 007831, chapter 'Cascading principle'

To activate the supervision path of the E3C011, the device "Fu supply ext. supply supervision" must be created in the tool SWE700A.

11.3Modules

Component

Order-No.

Description

Notes

H38G310

484930

Housing set

Door without cut-out

B2F020

470588

Converter 115/230VAC -> 29,6VDC 6A

 

E3C011

505479

Battery charging unit

 

Z3I470

484341

Cable set with card holder

 

AX1201

225487

Battery 12V / 27Ah

Capacity based battery make 'ALARMCOM' (FIAMM)

AX1210

475570

Battery 12V / 15Ah

 