Siemens FC700A manual Specify hardware required

Models: FC700A

1 70
Download 70 pages 19.31 Kb
Page 23
Image 23
Specify hardware required

Specify hardware required

9 Specify hardware required

In order to be able to specify the hardware required, system key data must be specified according the following procedure:

1.Specify number and type of detection lines Dependent on:

Detector series

Number of detectors, input and output modules

Building structure

2.Specify number and type of fire control installations Dependent on:

The fire protection installations to be activated

Location of the contacts (centralized or decentralized)

Individual types of contact (250VAC/10A or 30VDC/1A)

3.Specify number of operating units

Dependent on:

Operating concept

Parallel indicator panels, fire department control panels

4.Specify Accessories required

Dependent on:

Printer interface and printer

Remote transmission equipment

Gateway, etc.

5.Specify emergency power supply battery capacity Dependent on:

Total quiescent current

Required emergency current operating period (according to country)

Type of remote transmission

6.Provide configuration sheet/sheets (see chapter 29)

Dependent on:

Select sheets corresponding to the configuration

Complete everything

 

23

 

 

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004