16.1Terminology and abbreviations

Connection factors, line resistances and capacitances

16Connection factors, line resistances and capacitan- ces

16.1Terminology and abbreviations

KLK Collective line factor (SynoLINE600)

KMK Load factor for collective / conventional elements (SynoLINE600/300)

APLK addressable line factor (SynoLOOP)

APMK Load factor for addressable elements (SynoLOOP)

16.2Collective detection line

The modules E3M080 / DC1192 have the collective line factor KLK 25

Line resistance max. 250Ω, 150depending on evaluation required (line type 1, 11)

Line capacitance max. 4F

The entire line from the control unit to the last detector as well as all response indicator lines must be included when working out capacitance.

Details see document 007831

The total amount of detectors connected to one collective line should not ex- ceed a loading factor of 25

Element

Short designation

Load factor KMK

Smoke detector

OP620C/OP320C

1

Heat detector

HI620C/622C/HI320C/322C

1

Multisensor smoke detector

OH320C

1

Smoke detector

DO1101-Ex

1,6

Heat detector

DT1101-Ex

1

Infrared flame detector

DF1101-Ex

6

Infrared flame detector

DF1191/92

6

Linear smoke detector

DLO1191

25

Manual call point

DM1101, DM1103

1

In-/output module

DC1192

1

16.3Addressable detection line

The line module E3M111 has the addressable line factor APLK 128

Line resistance see chapter 16.4

Line capacitance see chapter 16.4

For a description of the E3M111 line module, see document 007831 'Hardware de- scription'.

The total amount of detectors connected to one addressable line should not exceed a loading factor of 128

Element

Short designation

Load factor APMK

Smoke detector

OP620A, OP320A

1

Heat detector

HI620A/622A, HI320A/322A

1

Multisensor smoke detector

OH620A, OH320A

1

Infrared flame detector

DF1191/92

5

Manual call point

MT320A, DM1133

1

Input module

EB322A

1

Output module

AB322A

2

In-/output module

ABI322A

2

In-/output module

DC1192, CB320A

3

Do not install lines longer than 2000m

38

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004