E) Power Line and grounding

 

N, L2

4

POWER SUPPLY

 

 

100 to 240 Vac

524 Vac/Vdc

R (S,T), L1

N, L2

 

R (S,T), L1

NOTE:

1)Before connecting the power line, check that the voltage is correct (see Model Number).

2)For supply connections use 16 AWG or larger wires rated for at least 75 °C.

3)Use copper conductors only.

4)Do not run input wires with power cables.

5)Polarity does not matter for 24 Vdc wiring.

6)The power supply input is not fuse protected. Please provide it externally.

Power Supply

Type

Current

Voltage

 

 

 

 

24 Vac/Vdc

T

500 mA

250 V

 

 

 

 

100/240 Vac

T

125 mA

250 V

 

 

 

 

PRELIMINARY HARDWARE SETTINGS

1)Remove the instrument from its case.

2)Set J106 according to the following table:

Input Type

 

 

J106

 

 

1-2

3-4

5-6

7-8

 

 

T/C, RTD,

 

 

 

 

 

0-60 mV, 12-60 mV

 

close

open

open

open

(standard configuration)

 

 

 

 

 

0-5 V, 1-5V

 

open

close

open

open

 

 

 

 

 

 

0-10V, 2-10 V

 

open

open

close

open

 

 

 

 

 

 

0-20 mA, 4-20 mA

 

open

open

open

close

 

 

 

 

 

 

Input CTTC R192=180K

 

 

 

 

SH120=Closed CH101=Open

When the fuse is damaged the instrument should be returned to your supplier to check the power supply.

7)Safety requirements for permanently connected equipment:

-Include a switch or circuit-breaker in the installation.

-Place the switch in close proximity to the equipment and within easy reach of the operator.

-Mark the switch as the disconnecting device for the equipment. NOTE: A single switch or circuit-breaker can drive more than one instrument.

8)When the NEUTRAL line is present, connect it to terminal 4.

9)To avoid shock and possible instrument damage, connect power last.