SSI America 7SL instruction manual P3 = Alarm Action, Alarm Standby Function, Off =, = Safety Lock

Models: 7SL

1 36
Download 36 pages 19.88 Kb
Page 18
Image 18

Example for P2 = H.A.A.c

(Alarm

(Hysteresis) threshold)

P3 = Alarm Action

(Skipped if option not is available or P1 = none)

dir =

Direct action

 

(Relay energized in alarm condition)

Alarm status* Relay No alarm status

ON

ALM LED

OFF

FLASH

ACK

FLASH

rEV

=

Reverse action

 

 

(Relay energized in non-alarm condition)

P4

=

Alarm Standby Function

(Skipped if option is not available or P1= none)

OFF =

Standby function disabled

On

=

Standby function enabled

ACK = Alarm acknowledgment from "AK" parameter or serial link.

*Alarm Status:Relay energized (P3 = dir) Relay de-energized (P3 =rEV)

Example for P2 = H.L.

If the alarm is programmed as band or deviation, this function masks the alarm condition at start up and at a “Su” setpoint change until the process variable reaches the alarm threshold, plus or minus hysteresis. This standby function masks a Process Alarm condition at start up until the process variable reaches the alarm threshold plus or minus hysteresis.

(Hysteresis)

Alarm status* Relay No alarm status

ON

ALM LED

OFF

FLASH

ACK

(Alarm

threshold)

FLASH

ACK

PF = Time Constant for Filter on Measured Value for Alarm Action

(Skipped if option is not available or P1 = none) Range: From 0 (filter OFF) to 8 seconds (First order filter with selected time constant.)

n 1 = Safety Lock

0= UNLOCKed. The device is always UNLOCKed and all parameters can be modified.

l

=

LOCKed. The device is always LOCKed and

 

 

no parameters can be modified

ACK = Alarm acknowledgment from "AK" parameter or serial link.

*Alarm Status:Relay energized (P3 = dir) Relay de-energized (P3 =rEV)

From 2 to 9999 = This number is a password, to be used in run time (see “nn”), to LOCK/UNLOCK the device.

1 8

7sl-2-00.p65

18

9/17/02, 2:40 PM

Page 18
Image 18
SSI America 7SL instruction manual P3 = Alarm Action, Alarm Standby Function, Off =, = Safety Lock